Model PD6400 High Voltage & Current Meter

Instruction Manual

11

RELAY
ASSIGNMENT

Each relay independently assigned to Ch-A, Ch-V, CH-P, or
Modbus

DEADBAND

0-100% of span, user programmable

HIGH OR LOW
ALARM

User may program any alarm for high or low trip point.
Unused alarm LEDs and relays may be disabled (turn off).

RELAY
OPERATION

Automatic (non-latching)
Latching (required manual acknowledge)
Pump alternation control (2 to 8 relays)
Sampling (based on time)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode

RELAY RESET

User selectable via front panel buttons, digital inputs, or PC

1.

Automatic reset only (non-latching), when the input
passes the reset point.

2.

Automatic + manual reset at any time (non-latching)

3.

Manual reset only, at any time (latching)

4.

Manual reset only after alarm condition has cleared (L)

Note: Front panel button or digital input may be assigned to

acknowledge relays programmed for manual reset.

TIME DELAY

0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay

FAIL-SAFE
OPERATION

Programmable and independent for each relay.

Note: Relay coil is energized in non-alarm condition.

In case of power failure, relay will go to alarm state.

BREAK
CONDITION
OPERATION

Relay condition when sensor break detected.
Programmable independently for each relay as On, Off, or
Ignore (maintain last condition).

AUTO
INITIALIZATION

When power is applied to the meter, relays will reflect the
state of the input to the meter.

Isolated 4-20 mA Transmitter Output

OUTPUT
SOURCE

Process channel A, V, or P, max or min for channel A, V, or
highest or lowest max or min of A and V, set points 1-8,
Modbus input, or manual control mode

SCALING RANGE 1.000 to 23.000 mA for any display range

CALIBRATION

Factory calibrated: 4.000 to 20.000 = 4-20 mA output

ANALOG OUT
PROGRAMMING

23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break

ACCURACY

± 0.1% of span ± 0.004 mA