Isolated 4-20 ma transmitter output – Precision Digital PD6400 User Manual
Page 11

Model PD6400 High Voltage & Current Meter
Instruction Manual
11
RELAY 
ASSIGNMENT 
Each relay independently assigned to Ch-A, Ch-V, CH-P, or 
Modbus 
DEADBAND
0-100% of span, user programmable
HIGH OR LOW 
ALARM 
User may program any alarm for high or low trip point. 
Unused alarm LEDs and relays may be disabled (turn off). 
RELAY 
OPERATION 
Automatic (non-latching) 
Latching (required manual acknowledge) 
Pump alternation control (2 to 8 relays) 
Sampling (based on time) 
Off (disable unused relays and enable Interlock feature) 
Manual on/off control mode 
RELAY RESET
User selectable via front panel buttons, digital inputs, or PC
1.
Automatic reset only (non-latching), when the input 
passes the reset point. 
2.
Automatic + manual reset at any time (non-latching)
3.
Manual reset only, at any time (latching)
4.
Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
TIME DELAY
0 to 999.9 seconds, on & off relay time delays 
Programmable and independent for each relay 
FAIL-SAFE 
OPERATION 
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
BREAK 
CONDITION 
OPERATION 
Relay condition when sensor break detected. 
Programmable independently for each relay as On, Off, or 
Ignore (maintain last condition). 
AUTO 
INITIALIZATION 
When power is applied to the meter, relays will reflect the 
state of the input to the meter. 
Isolated 4-20 mA Transmitter Output
OUTPUT 
SOURCE 
Process channel A, V, or P, max or min for channel A, V, or 
highest or lowest max or min of A and V, set points 1-8, 
Modbus input, or manual control mode 
SCALING RANGE 1.000 to 23.000 mA for any display range
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT 
PROGRAMMING 
23.000 mA maximum for all parameters: 
Overrange, underrange, max, min, and break 
ACCURACY
± 0.1% of span ± 0.004 mA