Modbus® rtu serial communications – Precision Digital PD6400 User Manual
Page 12

Model PD6400 High Voltage & Current Meter
Instruction Manual
12
TEMPERATURE
DRIFT
0.4 µA/
°C max from 0 to 65°C ambient,
0.8 µA/
°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals I+ & R: 24 VDC
± 10% @ 40mA. May be used to
power the 4-20 mA output or other devices. Refer to Figure
6 on page 18 and Figure 20 on page 25.
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply
Minimum
Maximum
24 VDC
10
Ω
700
Ω
35 VDC (external)
100
Ω
1200
Ω
Modbus® RTU Serial Communications
SLAVE ID
1 – 247 (Meter address)
BAUD RATE
300 – 19,200 bps
TRANSMIT
TIME DELAY
Programmable between 0 and 199 ms
DATA
8 bit (1 start bit, 1 or 2 stop bits)
PARITY
Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 second
TURN AROUND
DELAY
Less than 2 ms (fixed)
Note: Refer to the P
RO
V
U
®
Modbus Register Tables located at www.predig.com
for details.