beautypg.com

Table 30 outdoor condensing units, Table 31 indoor condensing units air-cooled, Table 32 indoor condensing units water-cooled – Emerson Liebert Challenger ITR User Manual

Page 58: Table 33 fan speed control condensers, Table 34 liebert lee-temp condensers, Table 30, Outdoor condensing units, Table 31, Indoor condensing units air-cooled, Table 32

background image

Electrical Data

50

Table 30

Outdoor condensing units

Electrical Data 50 Hz 35°C (95°F) Ambient

Voltage

Model

PFH066A-_L

200/230-3-50

FLA

24.1

380/415-3-50

FLA

13.2

Electrical Data 50 Hz 40°C (105°F) Ambient

Voltage

Model

PFH066A-_H

200/230-3-50

FLA

24.2

380/415-3-50

FLA

13.2

Electrical Data 50 Hz Quiet-Line 35°C (95°F)

Voltage

Model

PFHZ66A-_L

200/230-3-50

FLA

22.5

380/415-3-50

FLA

12.4

Table 31

Indoor condensing units air-cooled

Electrical Data 50 Hz 35°C (95°F) Ambient
Voltage

Model

MC_64A

380/415-3-50

FLA

13.7

1. Consult factory for 200/230 volts.

Table 32

Indoor condensing units water-cooled

Voltage

Model

MC_68W

380/415-3-50

FLA

10.0

1. Consult factory for 200/230 volts.

Table 33

Fan speed control condensers

35°C (95°F) Ambient (1 Phase - 50 Hz)

CSF104

Voltage

200/230

FLA

4.0

Table 34

Liebert Lee-Temp condensers

35°C (95°F) Ambient (3 Phase - 50 Hz)

CSL104

Voltage

200/230 380/

415

FLA

3.5

1.7

Table 35

Liebert Lee-Temp receiver heater pads; for use w/CSL condensers

Volts

230

Watts/Pad

150

FLA

0.7

Separate electrical source required for continuous operation of
single phase heater pads for Liebert Lee-Temp.