beautypg.com

0 electrical data, Lectrical, Liebert challenger itr electrical data – Emerson Liebert Challenger ITR User Manual

Page 51: Table 16 liebert challenger itr electrical data, 60 hz, Electrical data 43

background image

Electrical Data

43

15.0 E

LECTRICAL

D

ATA

Table 16

Liebert Challenger ITR electrical data

1

—60 Hz

Model Type

Self-Contained

Split System Evaporator or Chilled Water

BR067A, BR071WG, BM061G

BR060E, BR102C

Voltage

All Voltages Are 3 Phase Unless Noted Otherwise

208

230

460

575

208

230

460

575

With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note: See Table 17 for units w/SCR reheats.

2

)

Motor

1.5 hp (1.1 kW)

1.5 hp (1.1 kW)

FLA

68.0

65.0

32.3

24.6

60.6

55.4

28.1

24.6

WSA

83.6

80.0

39.7

30.8

75.8

69.3

35.1

30.8

OPD

90

90

40

30

80

70

40

35

Motor

2.0 hp (1.5 kW)

2.0 hp (1.5 kW)

FLA

69.8

66.6

33.1

25.2

62.4

57.0

28.9

25.2

WSA

85.4

81.6

40.5

31.5

78.0

71.3

36.1

31.5

OPD

90

90

45

30

80

80

40

35

Motor

3.0 hp (2.2 kW)

3.0 hp (2.2 kW)

FLA

72.9

69.4

34.5

26.4

65.5

59.8

30.3

26.4

WSA

88.5

84.4

41.9

33.0

81.9

74.8

37.9

33.0

OPD

90

90

45

35

90

80

40

35

Humidifier Only (Infrared or Steam Generating)
Motor

1.5 hp (1.1 kW)

1.5 hp (1.1 kW)

FLA

39.7

37.0

18.4

16.9

19.0

16.3

8.4

9.5

WSA

44.9

42.2

20.9

18.8

23.8

20.4

10.5

11.9

OPD

60

60

30

25

25

20

15

15

Motor

2.0 hp (1.5 kW)

2.0 hp (1.5 kW)

FLA

41.5

38.6

19.2

17.5

20.8

17.9

9.2

10.1

WSA

46.7

43.8

21.7

19.4

26.0

22.4

11.5

12.6

OPD

60

60

30

25

30

25

15

15

Motor

3.0 hp (2.2 kW)

3.0 hp (2.2 kW)

FLA

44.6

41.4

20.6

18.7

23.9

20.7

10.6

11.3

WSA

49.8

46.6

23.1

20.6

29.9

25.9

13.3

14.1

OPD

70

60

30

25

35

30

15

15

Electric Reheat Only (Note: See Table 17 for Self-contained units w/SCR reheats.

2

)

Motor

1.5 hp (1.1 kW)

1.5 hp (1.1 kW)

FLA

68.0

65.0

32.3

24.6

47.3

44.3

22.3

17.2

WSA

83.6

80.0

39.7

30.2

59.1

55.4

27.9

21.5

OPD

90

90

40

30

60

60

30

25

Motor

2.0 hp (1.5 kW)

2.0 hp (1.5 kW)

FLA

69.8

66.6

33.1

25.2

49.1

45.9

23.1

17.8

WSA

85.4

81.6

40.5

30.8

61.4

57.4

28.9

22.3

OPD

90

90

45

30

70

60

30

25

Motor

3.0 hp (2.2 kW)

3.0 hp (2.2 kW)

FLA

72.9

69.4

34.5

26.4

52.2

48.7

24.5

19.0

WSA

88.5

84.4

41.9

32.0

65.3

60.9

30.6

23.8

OPD

90

90

45

35

60

70

35

20

Without Electric Reheat and Humidifier
Motor

1.5 hp (1.1 kW)

1.5 hp (1.1 kW)

FLA

26.4

25.9

12.6

9.5

5.7

5.2

2.6

2.1

WSA

31.6

31.1

15.1

11.4

7.1

6.5

3.3

2.6

OPD

50

50

25

15

15

15

15

15

Motor

2.0 hp (1.5 kW)

2.0 hp (1.5 kW)

FLA

28.2

27.5

13.4

10.1

7.5

6.8

3.4

2.7

WSA

33.4

32.7

15.9

12.0

9.4

8.5

4.3

3.4

OPD

50

50

25

15

15

15

15

15

Motor

3.0 hp (2.2 kW)

3.0 hp (2.2 kW)

FLA

31.3

30.3

14.8

11.3

10.6

9.6

4.8

3.9

WSA

36.5

35.5

17.3

13.2

13.3

12.0

6.0

4.9

OPD

50

50

25

20

20

20

15

15

1.

Contact factory for 380-3-60 data.

2.

For Split System Evaporators with SCR reheat, use the values above.

The values above were calculated per UL Standard 1995.

FLA = Full Load Amps (Input Amps); WSA = Wire Size Amps (Minimum Supply Circuit Ampacity); OPD = Maximum Overcurrent Protective Device Size

RLA = Rated Load Amps; LRA = Locked Rotor Amps

* R = In the Row; M = In the Row with Econ-O-Coil