Table 6, Liebert challenger itr water cooled data, 60 hz – Emerson Liebert Challenger ITR User Manual

Page 36

background image

System Data

28

Table 6

Liebert Challenger ITR water cooled data, 60 Hz

System Type

BR = Horizontal Flow

Self-Contained

Split Systems

Indoor Unit

BR 071WG

BR 060E

Net Capacity Data

BTU/H

kW

BTU/H

kW

100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH

Total

82,900

24.3

79,000

23.1

Sensible

82,900

24.3

79,000

23.1

Non-Standard Flow Rates

2600 CFM

2400 CFM

95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH

Total

80,400

23.6

78,400

23.0

Sensible

80,400

23.6

78,400

23.0

90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH

Total

76,200

22.3

74,400

21.8

Sensible

76,200

22.3

74,400

21.8

85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH

Total

72,300

21.2

70,300

20.6

Sensible

72,300

21.2

70,300

20.6

80

°

F DB, 62.7

°

F WB (26.7

°

C DB, 17.1

°

C WB) 38% RH

Total

68,400

20.0

66,500

19.5

Sensible

68,400

20.0

66,500

19.5

80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH

Total

69,900

20.5

67,600

19.8

Sensible

55,700

16.3

54,900

16.1

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH

Total

65,200

19.1

63,100

18.5

Sensible

54,000

15.8

53,200

15.6

75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH

Total

63,600

18.6

61,500

18.0

Sensible

58,000

17.0

57,100

16.7

72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH

Total

62,500

18.3

60,500

17.7

Sensible

53,000

15.5

52,100

15.3

72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH

Total

61,100

17.9

59,200

17.3

Sensible

56,700

16.6

55,900

16.4

Fan Data (Blower A12x9AT)**

Standard Air, CFM (CMH)

2800 (4760)

2800 (4760)

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

1-1/2 (1.1)

Opt Fan Motor, hp (kW)

2 (1.5)

2 (1.5)

Ext Static, in. WG (Pa)

.3 (75)

.3 (75)

Evaporator Coil (V-Frame, at standard conditions)

Face Area, ft.

2

(m

2

)

6.67 (.62)

6.67 (.62)

Rows

4

4

Face Velocity, FPM (m/s)

405 (2.1)

405 (2.1)

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard

Capacity, inc. motor heat, BTU/H (element kW)

56,200 (15)

56,200 (15)

Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)

Capacity, inc. motor heat, BTU/H (kW)

88,700 (26.0)

88,700 (26.0)

Flow Rate, GPM (l/s)

5.0 (.32)

5.0 (.32)

Pressure drop, ft. (kPa)

16.9 (50.4)

16.9 (50.4)

Hot Gas Reheat - Optional (Includes standard air volume and optional fan motor)

Capacity, inc. motor heat, BTU/H (kW)

54,900 (16.1)

54,900 (16.1)

*

The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for

ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.

** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.