Table 20

Outdoor condensing units—Quiet-Line

Electrical Data 60 Hz, Quiet-Line, 95°F (35°C)
Voltage

Model

PFHZ67A-_L

208/230-3-60

FLA

21.1

WSA

25.9

OPD

45.0

380-3-60

FLA

12.5

WSA

15.2

OPD

25.0

460-3-60

FLA

10.9

WSA

13.4

OPD

20.0

575-3-60

FLA

8.8

WSA

10.8

OPD

15.0

Table 21

Indoor condensing units, air-cooled *

Electrical Data 60 Hz 95°F (35°C) Ambient

Voltage

Model

MC_65A

208/230-3-60

FLA

26.5

WSA

31.7

OPD

50.0

460-3-60

FLA

12.9

WSA

15.4

OPD

25.0

575-3-60

FLA

9.7

WSA

11.6

OPD

15.0

* Contact factory for 380-3-60 data.

Table 22

Indoor condensing units, water-cooled *

Voltage

Model

MC_69W

208/230-3-60

FLA

20.7

WSA

25.9

OPD

45.0

460-3-60

FLA

10.0

WSA

12.5

OPD

20.0

575-3-60

FLA

7.4

WSA

9.3

OPD

15.0