UPS Multi-Module Installation

51

3.4.4

Control Wires

For Liebert NX to NX dual bus configuration, interconnect the optional DBS cable between any DBS

ports of two parallel systems as illustrated in Figure 34.

Figure 34 Connections of a typical dual bus system utilising Load Bus Synch

3.4.5

Extended Dual Bus Synchronization Option (DBS Interface Box)

For Liebert NX to non- NX (whether another Liebert UPS range or not) dual bus configuration, one

DBS interface box shall be mounted on the non- Liebert NX UPS and one on the Liebert NX UPS. In

this situation, the other UPS system is always treated as a master and the following conditions are

covered:

• Master and slave are both on inverter
• Master on bypass, slave on inverter

NOTE
Example shown with ring control cables (“8”) for DSB applied to two 1+1 paralleled systems.

NOTE
Extended DBS interface box is also used for extending DBS cable length up to 150 metres for

DBS configuration between two groups of NX UPS systems.

UPS

X1-1

X1-2

X2-2

X2-1

Parallel Board

X4

X3

P5

P3

P4

P1

P2

X1-1

X1-2

X2-2

X2-1

Parallel Board

X4

X3

P5

P3

P4

P1

P2

8

X1-1

X1-2

X2-2

X2-1

Parallel Board

X4

X3

P5

P3

P4

P

1

P2

X1-1

X1-2

X2-2

X2-1

Parallel Board

X4

X3

P5

P3

P4

P

1

P2

8

UPS

B

Parallel System I

Parallel System II

DBS Cable

A