Single Module UPS Installation

14

1.8.4

Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 4 and Table 6)

Figure 4

Output dry contacts and EPO wiring for firmware before M162

Figure 5

EPO wiring for firmware M200 or later

1.8.5

Emergency Power Off Input

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel

or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 4, is the remote EPO input interface. The EPO has an NO/NC contact

point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1
If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the

auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm

2

(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.

Table 6

Output dry contact relays for firmware before M162

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay; normally open. Closed when bypass SCR is shorted.

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay; normally closed. Open when bypass SCR is shorted.

J21.2

INV_O

Inverter mode relay; normally open. Closed when UPS is in inverter mode.

J21.3

INV_S

Inverter mode relay center

J21.4

INV_C

Inverter mode relay; normally closed. Open when UPS is in inverter mode.

J25.2

ACF_O

Main input fault relay; normally open. Closed when main input is in fault.

J25.3

ACF_S

Main input fault relay center

J25.4

ACF_C

Main input fault relay; normally closed. Open when main input is in fault.

EPO-L

EPO-H

X2

X1

BF

P_

C

J21

J25

J25

BFP_S

BFP_O

INV_O

INV_S

INV_C

AC

F_C

AC

F

_

S

ACF_O

+12V

J13

J28

X2

EPO-NO

EPO-NC