Options—For Assembly Inside the UPS Cabinet

108

9.1.6

Battery Ground Fault Detection

In addition to any residual current device mounted externally and upstream the UPS or when

optional isolation transformers are fitted to the UPS, an optional residual battery current device can

be fitted to detect leakage current from the battery into the PE (Protective Earth) Residual current

range monitored: 30~3000mA.
Power supply voltage for the set: AC230V (L-N);
When a battery ground fault is detected, an alarm will appear on the UPS display panel.
An additional Dry contact fault Alarm signal is available for remote monitoring:

The Battery ground fault detection set contains one CT (current transformer) and one DC sensitive

residual current monitor. The connection of this set for UPS is illustrated as follows.

Figure 74 Battery ground fault detection set connections

The Battery Ground Fault Detection Set is assembled within the UPS cabinet.

Table 27

Dry contact fault alarm signal is available for remote monitoring

Terminal

Name

Definition

21

Common

Battery Ground Fault Detection – can be
programmed as Alarm or Pre-Alarm

22

NC

24

NO

BCB or

Contactor

Battery

Batt-N

Socket

Output
Phase

Output
Neutral

Current
Transformer
W1-A358

X

Monitor Board

-U2

UPS

IN DRY-X3

+12V

BtG

Battery Ground
Fault Detection
Resys B470
(AC230)

11

14

A1

A2

K1

K2

I2

I2

4

2