Operator Control Panel and Display

102

Auto start

After UPS was shutdown at EOD, inverter auto starts when utility restore

REC FLASH UPDATE

Rectifier firmware is being updated

INV FLASH UPDATE

Inverter firmware is being updated

MONITOR FLASH UPDATE

Monitor firmware is being updated

Input contactor fault

Input contactor fault

Contactor P.S. 1 fault

Contactor Power Supply board 1 Fault

Contactor P.S. 2 fault

Contactor Power Supply board 2 Fault

LBS abnormal

LBS is abnormal

DSP firmware error

The inverter firmware does not match with the rectifier firmware.

Input Fuse

Fail Internal AC Input Fuse to Rectifier Failed. Rectifier shuts down. Battery
discharges. Not applicable for 30-40kVA models.

Input Disconnect Open

AC mains input power switch open

Input Disconnect Closed

AC mains input power switch closed

Maint. Disconnect Open

Maintenance bypass power switch open

Maint. Disconnect Closed

Maintenance bypass power switch closed

Bypass Disconnect Open

AC bypass input power switch open

Bypass Disconnect Closed

AC bypass input power switch closed

Output Disconnect Open

UPS Output power switch open

Output Disconnect closed

UPS Output power switch closed

Input Inductor Overtemp.

Overheating of Rectifier input filter choke. Rectifier shuts down. Battery discharges.

Balancer Fault

Internal VDC(+) and VDC(-) off-set by over 50V exceeding the Inverter DC offset
compensation capacity. Inverter shuts down. Load transfers to bypass.

Balancer Over Current

Internal Inverter DC off-set balancing IGBT current rating exceeded 300%. Inverter
shuts down. Load transfers to bypass.

Balancer overtemp.

Inverter voltage offset control choke overheated. Inverter shuts down. Load
transfers to bypass.

Inv. Inductor Overtemp.

Inverter output filter choke overheated. Inverter shuts down. Load transfers to
bypass.

Batt. Converter Fault

Battery converter output voltage beyond limits or battery fuse failed. Battery
converter shuts down. Battety backup not available.

Batt. Conv. Over. Curr.

Battery converter overloaded. Battery converter shuts down. Battery backup not
available.

Batt. Converter Overtemp.

Overheating of Battery converter heatsinks. Battery converter shuts down. Battery
backup not available.

Output Disabled

UPS Output Disabled (test mode)

Table 23

UPS messages

Message

Description / Suggested Action (if any)