Technical Specifications

118

Table 38

Inverter output to critical load

Rated Power
(load pf 0.8 lag)

kVA

30

40

60

80

100

120

140

160

200

(load pf unity)

kW

24

32

48

64

80

96

112

128

160

(load pf 0.9 lead)

kVA

24

32

48

64

80

96

112

128

160

Rated AC Voltage

1

V (ac)

380/400/415 V

(three-phase, four-wire with neutral referenced to the bypass neutral)

Frequency

2

Hz

50 / 60

Overload

% rated

110% for 60 min
125% for 10 min

150% for 1 min

225% for 200 msec

Fault Current

% rated

320% current limitation for 200 msec

Non linear load capability

4

% rated

100%

Neutral current capability

% rated

170%

152%

135%

Steady state voltage stability 5

%

± 1 (balanced load),

± 2 (100% unbalanced load),

Transient voltage response

6

% ±

5

Total Harmonic Voltage Distortion
(THDV)

4

%

< 1 (linear load)

<3.5 (non linear load, 380V)

<4.0 (non linear load, 400V

< 4.5 (non linear load, 415V)

Synchronisation - Window
- Slew Rate (Max change rate of
synch frequency)

Hz

Rated frequency ± 2 Hz (selectable ± 0.5 to ± 3Hz)

Hz/sec

1 Hz/sec

selectable 0.1 to 3Hz/s (single UPS), 0.2Hz/sec (paralleled.UPS)

Inverter Voltage Tolerance

%V

(AC)

± 5

1.

Factory set to 400V – 380 or 415V selectable by commissioning engineer.

2.

Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Frequency converter operation also selectable.

3.

EN 50091-3 (1.4.50).

4.

Crest factor > 3:1 limited by IEC 62040-3 definition of non linear load.

5.

EN 50091-3 (4.3.4).

6.

EN 50091-3 (4.3.7) also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state output voltage within
half a cycle.