2 external protective devices, 3 power cables, External protective devices – Emerson Liebert NX 50 and 60 Hz User Manual

Page 59: Power cables

background image

UPS Multi-Module Installation

47

Figure 30 Dry contacts, multiple UPS modules with distribution panel

3.2.2

External Protective Devices

Refer to the instructions in 1.0 - Single Module UPS Installation.

3.2.3

Power Cables

The wiring of power cables is similar to that of single module system. The Bypass and the Main input

sources must be referenced to the same neutral potential and input earth leakage monitoring devices,

if installed, must be located upstream of the common neutral sinking point. Refer to the instructions

in 1.0 - Single Module UPS Installation.

NOTE
The length and specification of power cables including the bypass input cables and UPS output

cables should be the same. This facilitates load sharing when operating in bypass mode.

Input Distribution

UPS 1

M3 Board

X3

Ext. Maint. Ext. Out

UPS 2

M3 Board

X3

Ext. Maint. Ext. Out

UPS N

M3 Board

X3

Ext. Maint. Ext. Out

To Load

QUPS

QByp

Q1Ext

Q2Ext

QnExt