Battery Installation

44

Figure 27 Multiple temperature sensors, battery circuit breaker box and UPS module

NOTE:
1. Each probe consists one OT6-4 terminal and one precision temperature sensor that is

sealed in the OT6-4's terminal. The whole probe is supplied as one cable.

2. The type of temperature transport board illustrated in Figure 27 is TMP-2.
3. The signal cables in the Figure 27
must be shielded and double insulated.
4. The temperature monitoring cable must be less than 10m while the signal transmission

distance of the transport board must be less than 100m.

Temperature

Sensor

TMP-2

+

IN

-

NC

12V

GND

OUT

BCB Box

BCB Control

Board – C2

+12V

GND

OUT

X103

X105

X104

X106

X108

UPS

Monitor

Board

– U2

X7

-12V

GND

BAT-T

Temperature

Sensor

TMP-2

+

IN

-

NC

12V

GND

OUT

Temperature

Sensor

TMP-2

+

IN

-

NC

12V

GND

OUT

Temperature

Sensor

TMP-2

+

IN

-

NC

12V

GND

OUT

Type: W3 L = 5m

Type: W3 L = 30m

Cable W3 (L=5m) is packed with the temperature sensor.
Cable W3 (L=30m) is packed with the BCB box.