Battery Installation

40

2.6

Battery Circuit Breaker Box

The box contains a battery isolating circuit breaker and the circuit breaker controller board as also

mounted in the battery cabinet.
A range of battery circuit breaker boxes is available for use in installations where the battery is not

installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible

to the battery and connected to the UPS equipment as illustrated in Figure 25.
The battery circuit breaker box, used with the circuit breaker controller board, is required to protect

the battery from deep discharging and overcurrents. It also provides electrical isolation between the

UPS and the battery, permitting technical service personnel to reduce the risks involved in mainte-

nance work to a minimum. Inside the box are connection bars for power cables arriving from the UPS

and from the battery.

The control signal cable is connected to the circuit breaker controller board through the terminal

board.
The cable shield must be earthed to prevent induced noise affecting the control operation, and a sepa-

rate safety earth must be connected between the UPS unit and circuit breaker box.
The configurations in Table 9 are available, depending on the UPS power rating.

The BCB box contains a battery isolating circuit breaker and a circuit breaker controller board and

offers the following features:

• Short-circuit and End Of Discharge protection—The circuit-breaker (or internal UPS battery con-

tactor when fitted) automatically opens when the EOD voltage is reached

• UPS Emergency Stop compatibility—The circuit-breaker (or internal UPS battery contactor when

fitted) opens when the emergency stop button is pressed on the UPS front panel.

NOTE
The control cables from the UPS unit to the controller board must be made using a 5-core

shielded cable located in a separate conduit to that containing the battery power cables.

Table 9

UPS-circuit breaker configurations

UPS

Dimensions

HxWxD, mm (in)

Weight

kg (lb)

Circuit Breaker

30 to 40 kVA

558x378x180

(22x14.9x7)

21.5 (47.4)

125A 4p

60 to 80 kVA

200A 4p

100 to 120 kVA

25 (55)

400A 4p

140 to 160kVA

825x530x195

(32.4x21x7.7)

30 (66)

400A 4p

200kVA

32 (71)

500A 4p

Listed weights do not include packaging.

NOTE
30 to 40kVA UPS models fitted with internal battery and any UPS models fitted with a Battery

Start kit contain an internal UPS battery contactor for automatic connection and

disconnection of the batteries and the battery circuit breaker undervoltage coil is not used.

Refer to 2.5 - Battery Control for details