Technical Specifications

23

4.1

Agency and Certifications

Safety Standard: IEC/EN/AS 62040-1-1 incorporating applicable portions of IEC/EN/UL/AS 60950-1
Certification: CE and UL 60950-1:2003, First Edition CSA C22.2 No. 60950-1-03 1st Ed.
Electromagnetic Compatibility Standard: IEC/EN/AS 62040-2 incorporating applicable portions

of emission and immunity standards as detailed in Tables 20 and 21 below.
Table 20

Electromagnetic interference (EMI)—emission limits

Standard

IEC/EN/AS

Class

Harmonic Current

61000-3-2

-

Voltage Fluctuations & Flicker

61000-3-3

-

Conducted RFI

CISPR 22

A

Radiated RFI

CISPR 22

A

Table 21

Electromagnetic susceptibility (EMS)—immunity levels

Standard

IEC/EN/AS

Requirement

Level

Criterion

Electrostatic Discharge

61000-4-2

6 kV contact, 8 kV air

3

B

Radiated Electric Fields

61000-4-3

10 V/m

3

A

Fast Electrical Transients

61000-4-4

2 kV / 5 kHz (Power and Signal ports)

3

B

Surges

61000-4-5

Power port

2kV (common mode)

1kV (differential mode)

Signal port

1kV

3

B

Continuous Conducted Interfer.

61000-4-6

10V 3

A

Magnetic Field at Power Freq

61000-4-8

30A/m

-

B

Voltage Dips and Short

Interruptions

61000-4-11

70%Ut:

1ms, 3ms, 10ms

A

30ms, 100ms, 300ms, 1000ms

B

40%Ut:

1ms, 3ms

A

10ms, 30ms, 100ms, 300ms, 1000ms

B

0%Ut

1ms

A

3ms, 10ms, 30ms, 100ms, 300ms, 1000ms

B

Low Frequency Signals

61000-2-2

10V 140Hz-250Hz-360Hz

A