beautypg.com

0 technical specifications, Table 16 mechanical specifications, Table 17 environmental specifications – Emerson Liebert Remote Monitoring Panel User Manual

Page 26: Table 18 electrical specifications, Table 19 cable specifications, Echnical, Pecifications, Table 16, Mechanical specifications, Table 17

background image

Technical Specifications

22

4.0

T

ECHNICAL

S

PECIFICATIONS

Table 16

Mechanical specifications

Mechanical

Characteristics

Units

Value

Height

mm

100

Width mm

400

Depth

mm

290

Weight

kg

5.28

Ventilation

-

Air cooling

Cable entry

-

Left side

Color

-

Black

Protection

Grade

-

IP 20

Table 17

Environmental specifications

Environmental Characteristics

Units

Value

Operating Temperature

°C

0~40

Relative humidity

90% or less at 20°C

Acoustical noise

dBA

<32

Altitude of operation

m

<2000

Storage-transport temperature

°C

-25 ~70

Table 18

Electrical specifications

Electrical Characteristics

Units

Value

Rated input voltage

VAC

100,120, 220, 230, 240

Input voltage range

VAC

90-254

Input Frequency

Hz

50/60

Input frequency tolerance

Hz

47-67

Input Current

A

0.7A Max

Table 19

Cable specifications

Item

Specification

Input power cable *

3-pin plug containing L+N+E

RS-485 signal cable *

a shielded and twisted pair of 0.5 to 1 mm

2

wires

(16-20 AWG)

* These cables must be field-supplied.