2 led mimic power flow, Table 3 rectifier indicator, Table 4 battery indicator – Emerson Liebert Remote Monitoring Panel User Manual

Page 15: Table 5 bypass indicator, Table 6 inverter indicator, Table 7 load indicator, Table 8 status (alarm) indicator, 3 audible alarms—buzzer, Table 9 audible alarm key, Led mimic power flow

background image

Operation

11

3.2

LED Mimic Power Flow

The LEDs mounted on the mimic flow chart represent the various power paths and current UPS oper-

ational status.

3.3

Audible Alarms—

Buzzer

UPS activity is accompanied by the following sounds

Table 3

Rectifier indicator

Green

Rectifier in Normal Operation

Flashing

Green

Input AC Normal, but rectifier not operating

Red

Rectifier Failed

Off

Rectifier Not operating, Input AC Not Available or out of normal range

Table 4

Battery indicator

Green

Battery Normal, but discharging and powering the load

Flashing

Green

Battery End of Discharge pre-warning

Red

Battery abnormal (Failed, Absent or Polarity Reversed) or Battery

Converter abnormal

(Failed, overcurrent, overtemperature)

Off

Battery and Converter Normal, Battery charging

Table 5

Bypass indicator

Green

Load on Bypass power

Red

Bypass not available, out of normal range or Static bypass switch fault

Off

Bypass Normal, load not on bypass

Table 6

Inverter indicator

Green

Inverter Normal and powering the load

Flashing

Green

Inverter ON, starting up, synchronizing, or standing by (ECO mode)

Red

Inverter failed

Off

Inverter not operating

Table 7

Load indicator

Green

UPS output ON and Normal

Red

UPS output ON and Overloaded

Off

UPS output OFF.

Table 8

Status (Alarm) indicator

Green

Normal Operation

Yellow

UPS Warning e.g. AC Input Failure

Red

UPS fault (ex. Fuse or Hardware failure)

Table 9

Audible alarm key

Single beep

Direct Access key acknowledgement

One beep per second

UPS Warning, (ex. AC Input Failure)

Continuous beep

Fault, (ex. Fuse or Hardware Failure)