Operation

14

3.6

Detailed Description of Menu Items

The description that follows refers to the graphic LCD monitor window shown on Figure 14.
UPS System Window: This fixed-pane window displays current time and date and identifies the UPS,

its configuration and its status.

Menu and Data Window
Use the horizontal arrow keys to navigate between any of the selectable menu and data windows.

Table 11

UPS system window

Description

Explanation

Liebert NX

UPS family name

2005-10-22

YYYY-MM-DD (see

Settings menu for other date formats)

12:30:36

Current Time (24 hr HH:MM:SS format)

30kVA-3x3

30kVA = UPS rated output, 3 x 3 = 3-phase input and output

(Configuration)

Single, ECO, Master, Slave or Unit # 1

Single = single double-conversion unit

ECO = single stand-by unit with double-conversion fall-back

Master = master in a 1+1 Hot Stand By system

Slave = slave in a 1+1 Hot Stand By system

Unit # 1 = of max 6 double-conversion units in a parallel system

(Status)

Normal, Warning or Fault

Normal = UPS operating Normal

Warning = System attention required, e.g. AC Input Failure

Fault = UPS Fuse or Hardware Failure

Table 12

Descriptions of RMP menus and data window items

Menu

Type

Item Type

Explanation

Mains

(input)

L-N voltage (V)

Phase voltage

L-N current (A)

Phase current

Frequency (Hz)

Input frequency

L-L voltage (v

Line-line voltage

Power factor

Power factor

TX Input

L-N voltage (V)

Phase voltage

L-L voltage (V)

Line-line voltage

Bypass

L-N voltage (V)

Phase voltage

Frequency (Hz)

Bypass frequency

L-L voltage (A)

Line-line voltage

Output

L-N voltage (V)

Phase voltage

L-N current (A)

Phase current

Frequency (Hz)

Output frequency

L-L voltage (V)

Line-line voltage

Power factor

Power factor

TX Output

L-N voltage (V)

Phase voltage

L-L voltage (V)

Line-line voltage

Load

Sout (kVA)

Sout: Apparent power

Pout (kW)

Pout: Active power

Qout (kVAR)

Qout: Reactive power

Load level %

The percent of the UPS rating load

Crest factor

Output current Crest Factor

System

Sout (kVA)

Sout: Apparent power

Pout (kW)

Pout: Active power

Qout (kVAR)

Qout: Reactive power

Single unit, no parallel data

When configured as a single unit, UPS has only native load, no system

load.