Installing the device

Operating instructions Powador-gridsave_EN

Page 23

Authorised electrician

7.2.1.1 Output from the inverter

Recommended cable cross-sections for the inverter output and fuse rating of cables for fixed wiring accord-

ing to VDE 0100 part 430
The fuse rating for the cable is dependent on the cable cross-section.
max. 40A automatic circuit breaker

NOTE

When the line resistance is high (i.e. long grid-side cables), the voltage at the grid terminals of the

inverter will increase during feed-in to the grid. The inverter monitors this voltage. If the voltage

exceeds the country-specific grid overvoltage limit value, the inverter switches off.

Ensure that the conductor cross-sections are sufficiently large or that the cable lengths are suffi-

ciently short.

NOTE

In order to avoid asymmetries in the grid, systems with multiple battery systems should be designed

so that the inverters in the devices feed into the grid in differing phases.

Follow the connection conditions for the particular type of grid and the schematic illustration

below.

Country

and

grid-type

Grid monitoring

Required

monitoring

max. asymmetry between phases

L1,L2,L3

DE-NSP

Three-phase or single phase

phase unbalanced load 4.6 kVA

Table 5:

Grid-type-specific connection conditions

L1

L2

L3

N

Connection X1 Connection X1 Connection X1 Connection X1

L1 L2 L3 N PE

L1 L2 L3 N PE

L1 L2 L3 N PE

L1 L2 L3 N PE

Powador-gridsave inverter
1. L1 - L1 / L2 - L2 / L3 - L3
2. L1 - L2 / L2 - L3 / L3 - L1
3. L1 - L3 / L2 - L1 / L3 - L2
4. L1 - L1 / L2 - L2 / L3 - L3

Figure 14: Grid-side connection for systems with multiple battery systems with three-phase grid monitoring