2 installing components, Installing components – KACO Powador-gridsave User Manual
Page 17
Assembling the device
Operating instructions Powador-gridsave_EN
Page 17
Authorised electrician
0°
1000 mm
200 mm
200 mm
500 mm
min. carrying capacity
300 kg/m²
200 mm
200 mm
50 mm
Figure 9: Minimum clearances at the installation and assembly location
CAUTION
Risk of injury if the battery system tips over!
Risk of tipping due to high centre of gravity, particularly with the door open.
›
Anchor the device securely to the floor immediately after installation.
›
Open the housing door using the enclosed cabinet key only once the device has been securely
anchored.
510 mm
200
mm
200
mm
400 mm
12 mm
min. 110 mm
Designation
Hex head wood screw 8x80 DIN571-vz
Fischer dowel S12
Flat washer M8, galvanised, DIN9021-vz
Units
4
4
4
Figure 10: Dimensions for anchoring to the floor
Table 3:
Mounting parts
6.2
Installing components
CAUTION
Avoid improper handling!
Improper handling can cause damage to components.
›
Damaged components must not be installed.
›
Always put the plug-in modules down horizontally to avoid damage to the components.