A) grid connection, Warning, Action – KACO blueplanet 1502xi User Manual
Page 35

Page 32
32
31000770-02-112609 blueplanet Operating and Installation Instructions 1502xi - 5002xi
!
WARNING
Inputs and output circuits of this unit are isolated
from the enclosure. System grounding must be done
in accordance with the National Electrical Code
(NEC), ANSI/NFPA 70 and is the responsibility of
the installer.
ACTION
Guide the wiring through the conduit pipe.
Connect the wiring to the appropriate terminal labeled in
the connection box.
Torque Field Wiring Terminals to 20 in. lbs.
You must adhere to all mandatory safety regulations, the
currently required technical connection specifications of the
responsible power supply company, as well as to other gener-
ally applicable regulations.
!
WARNING
To connect the inverter, the AC and DC sides must
be disconnected from all power sources and secured
against being inadvertently energized.
(A) Grid Connection
Figure 5.17: Connection of the connection box
blueplanet 1502xi und 2502xi
Figure 5.18: Connection of the connection box
blueplanet 3502xi und 5002xi
Section 5 ·
Installation and Start-Up
DC Grounding Configuration
DC Connection Area
AC Connection Area
DC Grounding Configuration
DC Connection Area
AC Connection Area