3 technical data, Technical data – KACO blueplanet 1502xi User Manual
Page 20

Page 17
17
31000770-02-112609 blueplanet Operating and Installation Instructions 1502xi - 5002xi
Section 3 ·
Technical Data
3 Technical Data
Input – Electrical data
Model
1502xi
2502xi
3502xi
5002xi
DC rated power
1600 W
2650 W
3700 W
5300 W
Max. recommended
PV generator power
2000 W
3000 W
4000 W
6000 W
MPP range
125-400 V
200-450 V
200-510 V
200-510 V
No-load voltage
550 V
550 V
600 V
/ 550V*
600 V
/ 550 V*
Monitoring input voltage
Stand-by from
V
in
< 125 V
Stand-by from
V
in
< 200 V
Stand-by from
V
in
< 200 V
Stand-by from
V
in
< 200 V
Max. DC input current (Isc)
21.45 A
21.45 A
28 A
40 A
Polarity safeguard
Short-circuit diode
* Feed-In only, if PV-Voltage is smaller 550 V
Output – Electrical data
Model
1502xi
2502xi
3502xi
5002xi
Rated power
1500 W
2500 W
3500 W
5000 W
Maximum power
1650 W
2500 W
3500 W
5000 W
Line voltage
212 V-264 V @ 240 V
AC
184 V-228 V @ 208 V
AC
Rated current
6.5 A @ 240 V
AC
7.2 A @ 208 V
AC
10.4 A @ 240 V
AC
12.0 A @ 208 V
AC
14.6 A @ 240 V
AC
16.8 A @ 208 V
AC
20.8 A @ 240 V
AC
24.0 A @ 208 V
AC
Max. current
8.0 A @ 240 V
AC
8.0 A @ 208 V
AC
12.0 A @ 240 V
AC
12.5 A @ 208 V
AC
16.0 A @ 240 V
AC
17.0 A @ 208 V
AC
24.0 A @ 240 V
AC
24.0 A @ 208 V
AC
Power factor
0.99
Rated frequency
60.0 Hz
Frequency range
59.3 Hz-60.5 Hz
Distortion factor according to
VDE0838 part 2 (EN 61000-
3-2)
< 3% at rated power
< 5% over the entire range
Fault signal relay
Potential-free NO contact (make contact), max. 30 V / 3 A
S0 output
Open collector-output max. 30 V / 50 mA
Overvoltage protection
Varistors and spark gaps