beautypg.com

2 installing the inverter – KACO blueplanet 1502xi User Manual

Page 26

background image

Page 23

23

31000770-02-112609 blueplanet Operating and Installation Instructions 1502xi - 5002xi

– The unit is designed for vertical wall installation.

– Air must be allowed to circulate freely around the housing

and through the heat sink on the rear side.

– If the inverter is built into a switching cabinet or similar,

provide forced ventilation to ensure that heat is sufficiently
dissipated.

– The heat sink may reach a max. temperature of 194°F.

Therefore, mount the inverter only on walls made from
heat-resistant material.

– Ensure that the wall has adequate load-bearing capacity and

use appropriate installation material.

– Be sure to install the inverter in a sufficiently elevated place,

especially in areas prone to flooding, however it is important
to note that the minimum distance to ground is 3 feet when
mounted outdoors.

– Installation at eye level makes it easier to read the display.

– Mount the inverter in a location where the ambient tempe-

rature is ideally in the range of-4° to +104°F.

Section 5 ·

Installation and Start-Up

5.2 Installing the inverter

Figure 5.1: installing the wall bracket

1/4” lag bolt or equivalent