KACO blueplanet 1502xi User Manual
Page 21
Page 18
18
31000770-02-112609 blueplanet Operating and Installation Instructions 1502xi - 5002xi
Section 3 ·
Technical Data
Inverter – Electrical data
Model
1502xi
2502xi
3502xi
5002xi
Max. degree of efficiency
95.9% @ 240 V
AC
95.5% @ 208 V
AC
96.0% @ 240 V
AC
95.6% @ 208 V
AC
96.2% @ 240 V
AC
95.9% @ 208 V
AC
96.3% @ 240 V
AC
96.0% @ 208 V
AC
CEC degree of efficiency
95.5% @ 240 V
AC
95.0% @ 208 V
AC
95.5% @ 240 V
AC
95.0% @ 208 V
AC
95.5% @ 240 V
AC
95.5% @ 208 V
AC
95.5% @ 240 V
AC
95.0% @ 208 V
AC
Internal consumption
Night shutdown: 0.4 W @ 240 V
AC
/ 0.3 W @ 208 V
AC
Operation: < 5 W
Minimum grid-feed power
10 W
15 W
25 W
25 W
Maximum Output Fault
Current (AC) and Duration
30A / 100µs
50A / 100µs
70A / 100µs
96A/100 µs
Maximum Input Short Circuit
Current
21.45 A
21.45 A
28.0 A
40.0A
Maximum Input Source
Backfeed Current to Input
Source
0A
Synchronization In-Rush
Current
0A
Voltage and Frequency Trip
Time
< 160ms
Voltage Trip Limit Accuracy
1.5% of nominal value
Frequency Trip Limit Accuracy
± 0.06Hz
Trip Time Accuracy
± 0.1%
Circuit design
Galvanically isolating high frequency DC/DC converter with downstream self-
commutated inverter
Clock frequency
17kHz
Grid monitoring
complies with IEEE 1547