F7u parameters 4-28 – Yaskawa F7 Modbus User Manual
Page 67

F7U Parameters 4-28
Table 4.22– o2-04 Parameter Dependencies (400 VAC Class) Default Values
(Continued)
Model 4110
4132
4160
4185
4220
4300
kW
110
132
160
185
220
300
Min VAC
310
310
310
310
310
310
Max VAC
510
510
510
510
510
510
Prm
Unit
32
33
34
35
36
37
B3-03
Sec 2.0 2.0 2.0 2.0 2.0 2.0
B8-03 2.0 2.0 2.0 2.0 2.0 2.0
B8-04 36.23 32.79 30.13 30.57 27.13 21.76
C6-01
1 1 1 1 1 1
C6-02
3 2 2 2 1 1
C6-03
kHz
10.0 10.0 10.0 5.0 2.5 2.5
E2-01 A 190.0 223.0 270.0 310.0 370.0 500.0
E2-02 Hz 1.40 1.38 1.35 1.30 1.30 1.25
E2-03
% 49.0 58.0 70.0 81.0 96.0 130.0
E2-05
Ω .046 .035 .029 .025 .020 .014
E2-06
% 20.0 20.0 20.0 20.0 20.0 20.0
E2-07
50 50 50 50 50 50
E2-08
75 75 75 75 75 75
E2-10 W 2150 2350 2850 3200 3700 4700
E4-11
kW 110 132 160 185 220 300
E4-01 A 190.0 223.0 270.0 310.0 370.0 500.0
E4-02 Hz 1.40 1.38 1.35 1.30 1.30 1.25
E4-03
A 49.0 58.0 70.0 81.0 96.0 130.0
E4-05
Ω .046 .035 .029 .025 .020 .014
E4-06
% 20.0 20.0 20.0 20.0 20.0 20.0
E4-07
kW 110 132 160 185 220 300
L2-02
Sec 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Sec 1.7 1.7 1.8 1.9 2.0 2.1
L2-04
Sec 1.0 1.0 1.0 1.0 1.0 1.0
L8-02
°C
100 110 108 95 100 108