F7U Parameters 4-9
Table 4.5 – A Parameters
Mode
Name
Addr
Digital Operator
Text
Data
Parameter Range or
Data Description
Inc
Default
Run
V/f
V/f
wPG
OLV
FV
Dep
A2-22
011Bh
User Param 22
0h ~ 5ffh
1h
0h
A
A
A
A
A2-23
011Ch
User Param 23
0h ~ 5ffh
1h
0h
A
A
A
A
A2-24
011Dh
User Param 24
0h ~ 5ffh
1h
0h
A
A
A
A
A2-25
011Eh
User Param 25
0h ~ 5ffh
1h
0h
A
A
A
A
A2-26
011Fh
User Param 26
0h ~ 5ffh
1h
0h
A
A
A
A
A2-27
0120h
User Param 27
0h ~ 5ffh
1h
0h
A
A
A
A
A2-28
0121h
User Param 28
0h ~ 5ffh
1h
0h
A
A
A
A
A2-29
0122h
User Param 29
0h ~ 5ffh
1h
0h
A
A
A
A
A2-30
0123h
User Param 30
0h ~ 5ffh
1h
0h
A
A
A
A
A2-31
0124h
User Param 31
0h ~ 5ffh
1h
0h
A
A
A
A
A2-32
0125h
User Param 32
0h ~ 5ffh
1h
0h
A
A
A
A
►
B Parameters
Table 4.6 – B Parameters
Mode
Name
Addr
Digital Operator
Text
Data
Parameter Range or
Data Description
Inc
Default
Run
V/f
V/f
wPG
OLV
FV
Dep
0 Operator
1 Terminals
2 Serial
Com
3 Option
PCB
4 Pulse
Input
b1-01 0180h Reference
Source
5 CASE
Reference*
1 1
Q
Q
Q
Q
0 Operator
1 Terminals
2 Serial
Com
3 Option
PCB
4 EWS
b1-02 0181h
Run
Source
5 CASE
Sequence*
1 1
Q
Q
Q
Q
0
Ramp to Stop
1
Coast to Stop
2
DCInj to Stop
b1-03 0182h Stopping
Method
3 Coast
w/Timer
1 0
Q
Q
Q
Q
0 Enabled
b1-04 0183h
Reverse
Oper
1 Disabled
1 0
A
A
A
A
0
RUN at Freq Ref
1 STOP
2
RUN at Min Freq
b1-05 0184h Zero-Speed
Oper
3
RUN at Zero RPM
1 0
NA
NA
NA
A
0
2mS - 2 Scans
b1-06
0185h
Cntl Input Scans
1
5mS - 2 Scans
1 1
A
A
A
A
0
Cycle Extrn RUN
b1-07
0186h
LOC/REM RUN Sel
1
Accept Extrn RUN
1 0
A
A
A
A
0 Disabled
b1-08
0187h
RUN CMD at PRG
1 Enabled
1 0
A
A
A
A
b2-01
0189h
DCInj Start Freq
0.0 ~ 10.0 Hz
0.1 Hz
0.5 Hz
A
A
A
A
b2-02
018Ah
DCInj Current
0 ~ 100 %
1 %
50 %
A
A
A
NA
b2-03
018Bh
DCInj Time@Start
0.0 ~ 10.0 Sec
0.01 Sec
0.0 Sec
A
A
A
A
b2-04
018Ch
DCInj Time@Stop
0.0 ~ 10.0 Sec
0.01 Sec
0.5 Sec
A
A
A
A
b2-08
0190h
Field Comp
0 ~ 1000 %
1 %
0 %
NA
NA
A
NA
0 SpdsrchF
Disable
1 SpdsrchF
Enable
2 SpdsrchI
Disable
b3-01
0191h
SpdSrch at Start
3 SpdsrchI
Enable
1 2
A
A
A
NA
A1-02
b3-02
0192h
SpdSrch Current
0 ~ 200 %
1 %
120 %
A
NA
A
NA
A1-02
b3-03
0193h
SpdSrch Dec Time
0.1 ~ 10.0 Sec
0.1 Sec
2.0 Sec
A
NA
A
NA
b3-04
0194h
SpdSrch V/F
10 ~ 100 %
1 %
100 %
NA
NA
NA
NA
b3-05
0195h
Search Delay
0.0 ~ 20.0 Sec
0.1 Sec
0.2 Sec
A
A
A
A
b3-10
019Ah
Srch Detect Comp
1.0 ~ 1.2
0.01
1.1
A
NA
A
NA
0 Disabled
b3-14 019Eh Bidir
Search
Sel
1 Enabled
1 1
A
A
A
NA
b4-01
01A3h
Delay-ON Timer
0.0 ~ 3000.0 Sec
0.1 Sec
0.0 Sec
A
A
A
A
b4-02
01A4h
Delay-OFF Timer
0.0 ~ 3000.0 Sec
0.1 Sec
0.0 Sec
A
A
A
A
0 Disabled
1 Enabled
2 Enabled
3 Fref+PI
b5-01 01A5h
PID
Mode
4 Fref+PI
1 0
A
A
A
A
b5-02
01A6h
PID Gain
0.0 ~ 25.0
0.01
1
R
A
A
A
A
b5-03
01A7h
PID I Time
0.0 ~ 360.0 Sec
0.1 Sec
1.0 Sec
R
A
A
A