F7u parameters 4-18 – Yaskawa F7 Modbus User Manual
Page 57

F7U Parameters 4-18
Table 4.11 – H Parameters
Mode
Name
Addr
Digital Operator
Text
Data
Parameter Range or
Data Description
Inc
Default
Run
V/f
V/f
wPG
OLV
FV
Dep
0 0-10
VDC
H3-04
0413h
Term A3 Signal
1
-10 +10 VDC
1
0
A A A A
0 Frequency
Bias
1 Frequency
Gain
2 Aux
Reference
3 Voltage
Bias
4 Acc/Dec
Change
5
DC Brake Current
6 Overtorque
Level
7
Stall Prev Level
8 Ref
Lower
Limit
9 Jump
Frequency
10 PI
Feedback
11
PI Set Point
12
Frequency Bias 2
13 MotorTemperature
14
Fwd Torque Limit
15
Rev Torque Limit
16
Regen Torq Limit
17 Torque
Reference
18 Torque
Comp
19 Torque
Limit
20 PI
Differential
21 Not
Used
22
CASE AI 1
H3-05
0414h
Terminal A3 Sel
23
CASE AI 2
1
02h
A A A A
H3-06
0415h
Terminal A3 Gain
0.0 ~ 1000.0 %
0.1 %
100.00 %
R
A
A
A
A
H3-07
0416h
Terminal A3 Bias
-100.0 ~ 100.0 %
0.1 %
0.00 %
R
A
A
A
A
0 0-10
VDC
1
-10 +10 VDC
H3-08
0417h
Term A2 Signal
2 4-20
mA
1
2
A A A A
0 Frequency
Bias
1 Frequency
Gain
2 Aux
Reference
3 Voltage
Bias
4 Acc/Dec
Change
5
DC Brake Current
6 Overtorque
Level
7
Stall Prev Level
8 Ref
Lower
Limit
9 Jump
Frequency
10 PI
Feedback
11
PI Set Point
12
Frequency Bias 2
13 MotorTemperature
14
Fwd Torque Limit
15
Rev Torque Limit
16
Regen Torq Limit
17 Torque
Reference
18 Torque
Comp
19 Torque
Limit
20 PI
Differential
21 Not
Used
22
CASE AI 1
H3-09
0418h
Terminal A2 Sel
23
CASE AI 2
1
0h
A A A A
H3-10
0419h
Terminal A2 Gain
0.0 ~ 1000.0 %
0.1 %
100.00 %
R
A
A
A
A
H3-11
041Ah
Terminal A2 Bias
-100.0 ~ 100.0 %
0.1 %
0.00 %
R
A
A
A
A
H3-12
041Bh
Filter Avg Time
0.0 ~ 2.0 Sec
0.01 Sec
0.03 Sec
A
A
A
A
0 Std
Fan
Cooled
1 Std
BlowerCooled
2 Vector
Motor
3 Frequency
Ref
4 Output
Freq
5 Output
Current
6 Control
Method
7 Motor
Speed
8 Output
Voltage
9
DC Bus Voltage
10 Output
kWatts
11 Torque
Reference
12
Input Term Sts
13
Output Term Sts
14
Int Ctl Sts 1
H4-01
041Dh
Terminal FM Sel
15 Elapsed
Time
1
02h
A A A A