L parameters - protection, F7u parameters 4-20 – Yaskawa F7 Modbus User Manual
Page 59

F7U Parameters 4-20
Table 4.11 – H Parameters
Mode
Name
Addr
Digital Operator
Text
Data
Parameter Range or
Data Description
Inc
Default
Run
V/f
V/f
wPG
OLV
FV
Dep
0
Ramp to Stop
1
Coast to Stop
2 Fast-Stop
H5-04
0428h
Serial Fault Sel
3 Alarm
Only
1
3
A A A A
0 Disabled
H5-05
0429h
Serial Flt Dtct
1 Enabled
1
1
A A A A
H5-06
042Ah
Transmit WaitTIM
5 ~ 65 ms
1 ms
5 ms
A
A
A
A
0 Disabled
H5-07
042Bh
RTS Control Sel
1 Enabled
1
1
A A A A
0 Frequency
Ref
1 PI
Feedback
H6-01
042Ch
Pulse Input Sel
2
PI Set Point
1
0
A A A A
H6-02
042Dh
Pulse In Scaling
1000 ~ 32000 Hz
1 Hz
1440 Hz
R
A
A
A
A
H6-03
042Eh
Pulse Input Gain
0.0 ~ 1000.0 %
0.1 %
100.00 %
R
A
A
A
A
H6-04
042Fh
Pulse Input Bias
-100.0 ~ 100.0 %
0.1 %
0.00 %
R
A
A
A
A
H6-05
0430h
Pulse In Filter
0.0 ~ 2.0 Sec
0.01 Sec
0.1 Sec
R
A
A
A
A
H6-06
0431h
Pulse Moni Sel
See H4-01
1
02h
R
A
A
A
A
H6-07
0432h
Pulse Moni Scale
0 ~ 32000 Hz
1 Hz
1440 Hz
R
A
A
A
A
►
L Parameters - Protection
Table 4.12 – L Parameters
Mode
Name
Addr
Digital Operator
Text
Data
Parameter Range or
Data Description
Inc
Default
Run
V/f
V/f
wPG
OLV
FV
Dep
0 120
Hz
1 180
Hz
2 Custom
V/F
L1-01 0480h MOL
Fault
Select
3
Custom w/o limit
1
1
Q Q Q Q
L1-02
0481h
MOL Time Const
0.1 ~ 5.0 min
0.1 min
1.0 min
A
A
A
A
0
Ramp to Stop
1
Coast to Stop
2 Fast-Stop
L1-03
0482h
Mtr OH Alarm Sel
3 Alarm
Only
1
3
A A A A
0
Ramp to Stop
1
Coast to Stop
L1-04
0483h
Mtr OH Fault Sel
2 Fast-Stop
1
1
A A A A
L1-05
0484h
Mtr Temp Filter
0.0 ~ 10.0 Sec
0.01 Sec
0.2 Sec
A
A
A
A
0 Disabled
1
PwrL RideThru t
L2-01 0485h
PwrL
Selection
2
CPU Power Active
1
0
A A A A
L2-02
0486h
PwrL Ridethru t
0.0 ~ 25.5 Sec
0.1 Sec
0.1 Sec
A
A
A
A
L2-03
0487h
PwrL Baseblock t
0.1 ~ 5.0 Sec
0.1 Sec
0.5 Sec
A
A
A
A
L2-04
0488h
PwrL V/F Ramp t
0.0 ~ 5.0 Sec
0.1 Sec
0.3 Sec
A
A
A
A
L2-05
0489h
PUV Det Level
150 ~ 210 VDC
1 VDC
190 VDC
A
A
A
A
A1-02
L2-06
048Ah
KEB Decel Time
0.0 ~ 200.0 Sec
0.1 Sec
0.0 Sec
A
A
A
A
L2-07
048Bh
UV Return Time
0.0 ~ 25.5 Sec
0.1 Sec
0.0 Sec
A
A
A
A
L2-08
048Ch
KEB Frequency
0 ~ 300 %
100 %
A
A
A
A
0 Disabled
1 General
Purpose
L3-01
048Fh
StallP Accel Sel
2 Intelligent
1 1
A
A
A
NA
L3-02
0490h
StallP Accel Lvl
0 ~ 200 %
1 %
150 %
A
A
A
NA
L3-03
0491h
StallP CHP Lvl
0 ~ 100 %
1 %
50 %
A
A
A
NA
0 Disabled
1 General
Purpose
2 Intelligent
L3-04
0492h
StallP Decel Sel
3
Stall prev w/R
1
1
Q Q Q Q
0 Disabled
1
Decel Time 1
L3-05
0493h
StallP Run Sel
2
Decel Time 2
1 1
A
A
NA
NA
L3-06
0494h
StallP Run Level
30 ~ 200 %
1 %
160 %
A
A
NA
NA
0 Disabled
L3-11 04C7h
OV
Inhibit
Sel
1 Enabled
1 0
NA
NA
A
A
L3-12
04C8h
OV Inhbt VoltLvl
350 ~ 390 V
1 V
380 V
NA
NA
A
A
A1-02
L4-01
0499h
Spd Agree Level
0.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
A
A
C6-01
L4-02
049Ah
Spd Agree Width
0.0 ~ 20.0 Hz
0.1 Hz
2.0 Hz
A
A
A
A
L4-03
049Bh
Spd Agree Lvl+-
-400.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
A
A
C6-01
L4-04
049Ch
Spd Agree Wdth+-
0.0 ~ 20.0 Hz
0.1 Hz
2.0 Hz
A
A
A
A
0 Stop
L4-05 049Dh
Ref
Loss
Sel
1
Run@ 80 % PrevRef
1
0
A A A A
L4-06
04C2h
Fref at Floss
0.0 ~ 100.0 %
0.1 %
80.00 %
A
A
A
A