Yaskawa GPD 515-G5 Modbus RTU User Manual
Page 62

7-26
Registers
Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
500h
o1-01
Monitor Selection
4 to 28, 32, 33 (2)
6
501h
o1-02
Monitor Selection after Power-up
1
Frequency Reference
2
Output Frequency
1
3
Output Current
4
Selected Monitor
502h
o1-03
Digital Operator Display Selection
0 to 39999
0
503h
o1-04
Digital Operator Display Units
0
Hz
0
1
RPM
504h
o1-05
Parameter / Address Display
0
Parameter Number
0
Selection
1
Modbus Address
505h
o2-01
LOCAL / REMOTE Key
0
Disabled
1
Selection
1
Enabled
506h
o2-02
STOP Key Function during
0
Disabled
1
Remote Run
1
Enabled
507h
o2-03
User Parameter Default Value
0
Disabled
1
Set Default
0
2
Clear all
508h
o2-04
kVA Selection (Drive Model No.)
0 to FFh
(1)
509h
o2-05
Digital Operator
0
Drive accepts freq. after ENTER key
0
ìMotor Operated Potî
1
Drive accepts freq. immediately
Notes (for this page only):
1. Not initialized. Initial value differs depending on the drive capacity.
2. Range shown is for flash software version‘1030’ and CPU version ‘30’. Range differs for previous versions.