7-10
Registers
Drive Parameter Registers (U2-XX / Fault Trace and U3-XX / Fault History) (continued)
REGISTER
PARAMETER
PARAMETER
PARAMETER
BIT
LIMITS / DESCRIPTION
(in hex)
FUNCTION
SETTING
NO.
08Ch
U2-13
Drive Status at Fault
0
Running at the time of fault
1
Zero-Speed at the time of fault
2
Reverse Running at the time of fault
3
Reset Signal Input at the time of fault
4
Speed Agree at the time of fault
5
Drive Operation Ready at the time of fault
6
Minor Fault
7
Major Fault
08Dh
U2-14
Elapsed Time at Fault
Elapsed Time at the time of fault (in hrs.)
090h
U3-01
Last Fault
Code of the most recent fault (1)
091h
U3-02
Fault Message 2
Code of the second to most recent fault (1)
092h
U3-03
Fault Message 3
Code of the third to most recent fault (1)
093h
U3-04
Fault Message 4
Code of the fourth to most recent fault (1)
094h
U3-05
Elapsed Time 1
Elapsed Time at the most recent fault occurrence
095h
U3-06
Elapsed Time 2
Elapsed Time at the second to most recent fault occurrence
096h
U3-07
Elapsed Time 3
Elapsed Time at the third to most recent fault occurrence
097h
U3-08
Elapsed Time 4
Elapsed Time at the fourth to most recent fault occurrence
Notes (for this page only):
1. List of Drive Error Codes can be found in Chapter 8, Error Codes and Troubleshooting.