Drive parameter registers (u1-xx / monitor only) – Yaskawa GPD 515-G5 Modbus RTU User Manual

Page 43

background image

7-7

Registers

Drive Parameter Registers (U1-XX / Monitor Only)

REGISTER

PARAMETER

PARAMETER

PARAMETER

BIT

LIMITS / DESCRIPTION

(in hex)

FUNCTION

SETTING

NO.

020h

U1-01

Frequency Reference

Frequency Reference of drive (0.1 Hz) (1)

021h

U1-02

Output Frequency

Output Frequency of drive (0.1 Hz) (1)

022h

U1-03

Output Current

Drive rating / 8192

023h

U1-04

Control Method

0

V/f Control

1

V/f with PG Feedback

2

Open Loop Vector

3

Flux Vector

024h

U1-05

Motor Speed

Motor Speed (in 0.1 Hz)

025h

U1-06

Output Voltage

Output Voltage (in 0.1 V)

026h

U1-07

DC Bus Voltage

DC Bus Voltage (in 1 V)

027h

U1-08

Output Power

Output Power (in 0.1 kW)

028h

U1-09

Torque Reference

Torque Reference (in 0.1%)

029h

U1-10

Input Terminal Status

0

Input Terminal 1 closed

1

Input Terminal 2 closed

2

Input Terminal 3 closed

3

Input Terminal 4 closed

4

Input Terminal 5 closed

5

Input Terminal 6 closed

6

Input Terminal 7 closed

7

Input Terminal 8 closed

02Ah

U1-11

Output Terminal Status

0

Control Circuit terminals 9 & 10: ìClosedî

1

Control Circuit terminals 25 & 27: ìClosedî

2

Control Circuit terminals 26 & 27: ìClosedî

3-6

not used

7

Control Circuit terminals 18 & 20: ìClosedî

Notes (for this page only):

1. Scaling depends on setting of o1-03.