7-19

Registers

Drive Parameter Registers (Read/Write) (continued)

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

380h

F1-01

Encoder (PG) Constant

0 to 60000 ppr

600

381h

F1-02

Operation Selection at PG Open

0

Ramp to Stop

Circuit

1

Coast to Stop

1

2

Fast-Stop

3

Alarm Only

382h

F1-03

Operation Selection at Overspeed

0

Ramp to Stop

1

Coast to Stop

1

2

Fast-Stop

3

Alarm Only

383h

F1-04

Operation Selection at Speed

0

Ramp to Stop

Deviation

1

Coast to Stop

3

2

Fast-Stop

3

Alarm Only

384h

F1-05

PG Rotation

0

Counter-clockwise

0

1

Clockwise

385h

F1-06

PG Division Rate (PG Pulse Monitor)

1 to 132 (effective only with PG-B2 control board)

1

386h

F1-07

Integral Value during Accel/Decel

0

Disabled

0

Selection

1

Enabled

387h

F1-08

Overspeed Detection Level

0 to 120%

115

388h

F1-09

Overspeed Detection Delay Time

0.0 to 2.0 seconds

(1)

389h

F1-10

Excessive Speed Deviation

Detection Level

0 to 50%

10

38Ah

F1-11

Excessive Speed Deviation

Detection Delay Time

0.0 to 10.0 seconds

0.5

38Bh

F1-12

Number of PG Gear Teeth 1

0 to 1000

0

38Ch

F1-13

Number of PG Gear Teeth 2

0 to 1000

0

397h

F1-14

PG Open Detection Time

0 to 10.0 seconds

2.0

Notes (for this page only):

1. Initial value differs depending on the control method (A1-02).