Yaskawa GPD 515-G5 Modbus RTU User Manual
Page 61

7-25
Registers
Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
49Ch
L6-05
Torque Detection Level 2
0 to 300%
150
49Dh
L6-06
Torque Detection Time 2
0.0 to 10.0 seconds
0.1
49Eh
L7-01
Forward Torque Limit
0 to 300%
200
49Fh
L7-02
Reverse Torque Limit
0 to 300%
200
4A0h
L7-03
Forward Regenerative Torque Limit
0 to 300%
200
4A1h
L7-04
Reverse Regenerative Torque Limit
0 to 300%
200
4A2-4A3h
Reserved
4A4h
L8-01
Internal Dynamic Braking
0
Not Provided
0
Resistor Protection
1
Provided
4A5h
L8-02
oH (Overheat) Protection Alarm Level
50 to 110
o
C
100
4A6h
L8-03
Operation Selection after oH
0
Ramp to Stop
(Overheat) Pre-alarm
1
Coast to Stop
3
2
Fast-stop
3
Alarm Only
4A7h
Reserved
4A8h
L8-05
Input Open-phase Protection
0
Disabled
0
Selection
1
Enabled
4A9h
Reserved
4AAh
L8-07
Output Open-phase Protection
0
Disabled
0
Selection
1
Enabled
4AB-4B1h
Reserved