9 CDBR Braking Unit and LKEB Braking Resistor Selection

YASKAWA ELECTRIC TOBP C720600 01C 1000-Series Option CDBR-†D, LKEB-† Installation Manual

69

Figure 32

Figure 32 Fault Circuit Connection Diagram D

(CDBR Braking Unit and LKEB Braking Resistor Unit in parallel)

<1> 200 V class drives do not require a control circuit transformer.

<2> Set L3-04 to 0 or 3 to disable Stall Prevention during deceleration when using an LKEB Braking Resistor Unit.

The motor may not stop within the deceleration time if this setting is not changed.

<3> When connecting multiple LKEB Braking Resistor units, wire the thermal relay trip contacts in parallel.

P

B

1

2

1

2

P

B

MA MB MC

EA EB EC

<2>

ELCB (MCCB)

R

T

S

MC

R/L

1

S/L

2

T/L

3

3

M

U/T

1

V/T

2

W/T

3

ON

OFF

THRX

SA

1

2

TRX

MC MA

MC

TRX

MC

SA

SA

THRX

MC

MB

<1>

B1

B2

B

P

1

2

SC

SB

Braking resistor
overheat switch

(thermal relay trip)

CDBR transistor
short-circuit
detection output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
(to customer circuit)

Fault output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
(to customer circuit)

Level

Sensor

CDBR Braking Unit

LKEB Braking
Resistor Unit

3-phase

Drive

Wiring sequence should shut off power to the drive
when a CDBR transistor short-circuit detection
output is triggered or a braking resistor unit
overheat switch is triggered.

Fault relay contact

Braking resistor

overheat switch

(thermal relay trip)

(Ground)

<3>

<3>

TOBP_C720600_01C_3_0_E.fm 69 ページ 2013年11月1日 金曜日 午後2時50分