beautypg.com

Efer to, Table 9, 6 electrical installation – Yaskawa AC Drive-Option BRAKING UNIT-CDBR Spec.D User Manual

Page 49

background image

6 Electrical Installation

YASKAWA ELECTRIC TOBP C720600 01C 1000-Series Option CDBR-†D, LKEB-† Installation Manual

49

CDBR Braking Unit Terminal Functions

This section explains terminal functions and specifications to ensure safe and proper

installation of the CDBR Braking Unit.

Table 9 CDBR Braking Unit Main Circuit Terminals

Terminal

Block

Terminal No.

Terminal Name

Specification

TB3

Main Circuit Negative
Terminal

Connects to the negative terminal on the drive.

Main Circuit Positive
Terminal

Connects to the 3 terminal on the drive.

TB4

B1

Main Circuit B1
Terminal

Connects to the B1 terminal on the LKEB braking resistor
unit. May also connect to a braking resistor terminal of a
non-Yaskawa resistor unit.

B2

Main Circuit B2
Terminal

Connects to the B2 terminal on the LKEB braking resistor
unit. May also connect to a braking resistor terminal of a
non-Yaskawa resistor unit.

Grounding terminal

For 200 V class: 100

Ω or less

For 400 V class and 600 V class: 10

Ω or less

TOBP_C720600_01C_3_0_E.fm 49 ページ 2013年11月1日 金曜日 午後2時49分