Wire Size and Torque Specifications
Select appropriate wire type and gauges from
Note: 1. For main circuit terminal wiring ( , , B1, B2), UL approval requires using UL Listed copper wires
(rated at 75
°C (167°F)).
2. Use the wires with recommended gauge to make models 2022D, 2037D, 4030D, 4045D, and 5037D
conform to IP20 enclosure requirements.
Table 11 Wire Gauge and Torque Specifications
Model
CDBR- Terminal
For Japan
For U.S.A.
For Europe and
China
Screw
Size
Tightening
Torque
N
x
m
(lb.in.)
Recommended
Gauge
mm
2
Applicable
Gauge
mm
2
Recommended
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommended
Gauge
mm
2
Applicable
Gauge
mm
2
2022D
2037D
4030D
4045D
5037D
, ,
B1, B2
5.5
5.5 to 8.0
10
10 to 8
6
6 to 10
M5
2.7 to 3.0
(23.9 to 26.6)
IN1, IN2,
OUT1,
OUT2,
SB, SC,
MA, MB,
MC, EA,
EB, EC
0.75
0.75 to
2.00
18
18 to 14
0.75
0.75 to
2.50
M3.5
0.8 to 1.0
(7.1 to 8.9)
5.5
5.5 to 8.0
8
8
6
6 to 10
M5
2.0 to 2.5
(17.7 to 22.1)
2055D
4090D
, ,
B1, B2
14
14
8
8 to 6
10
10 to 16
M5
2.0 to 2.5
(17.7 to 22.1)
IN1, IN2,
OUT1,
OUT2,
SB, SC,
MA, MB,
MC, EA,
EB, EC
0.75
0.75 to
2.00
18
18 to 14
0.75
0.75 to
2.50
M3.5
0.8 to 1.0
(7.1 to 8.9)
14
14
6
6
10
10 to 16
M5
2.0 to 2.5
(17.7 to 22.1)
2110D
4220D
5110D
5300D
, ,
B1, B2
30
30 to 38
3
3 to 2
35
35
M8
8 to 10
(70.8 to 88.5)
IN1, IN2,
OUT1,
OUT2,
SB, SC,
MA, MB,
MC, EA,
EB, EC
0.75
0.75 to
2.00
18
18 to 14
0.75
0.75 to
2.50
M3.5
0.8 to 1.0
(7.1 to 8.9)
22
22 to 30
3
3 to 2
25
25 to 35
M8
8 to 10
(70.8 to 88.5)
TOBP_C720600_01C_3_0_E.fm 51 ページ 2013年10月7日 月曜日 午後2時20分