beautypg.com

Yaskawa AC Drive-Option BRAKING UNIT-CDBR Spec.D User Manual

Page 68

background image

9 CDBR Braking Unit and LKEB Braking Resistor Selection

68

YASKAWA ELECTRIC TOBP C720600 01C 1000-Series Option CDBR-†D, LKEB-† Installation Manual

Figure 31

Figure 31 Fault Circuit Connection Diagram C (CDBR Braking Unit in parallel)

Note: Contact your Yaskawa representative or the nearest Yaskawa sales office when using the CDBR

Braking Unit (CDBR-†D) with earlier models (CDBR-† or CDBR-†B)

<1> 200 V class drives do not require a control circuit transformer.

<2> Set L3-04 to 0 or 3 to disable Stall Prevention during deceleration when using an LKEB Braking Resistor Unit.

The motor may not stop within the deceleration time if this setting is not changed.

<3> Connect directly to the drive terminal or install a terminal block.

<4> When using more than one CDBR Braking Unit connected in parallel, set one of the CDBR Braking Units as the

master, and set the others as slaves.

MA MB MC EA EB EC

MA MB MC EA EB EC

OUT1

OUT2

IN1

IN2

3

1

P

2

B

+

B1

B2

B

P

1

2

+

OUT1

OUT2

IN1

(Ground)

IN2

+

B1

B2

<4>

<4>

<2>

<2>

<3>

<3>

ELCB (MCCB)

R

T

S

MC

R/L

1

S/L

2

T/L

3

ON

OFF

THRX

SA

1

2

TRX

MC MA

MC

TRX

MC

SA

SA

THRX

MC

MB

<1>

SC

SB

SC

SB

Wiring sequence should shut off power to the
drive when a CDBR transistor short-circuit
detection output is triggered or a braking
resistor unit overheat switch is triggered.

Fault relay contact

Braking resistor

overheat switch

(thermal relay trip)

Drive

Braking resistor
overheat switch

(thermal relay trip)

LKEB
Braking
Resistor
Unit

LKEB
Braking
Resistor
Unit

CDBR Braking

Unit 2 (slave)

CDBR Braking

Unit 1 (master)

IN (Slave)

OUT (Master)

IN (Slave)

OUT (Master)

Fault output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
(to customer circuit)

CDBR transistor
short-circuit
detection output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
(to customer circuit)

Fault output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
(to customer circuit)

CDBR transistor
short-circuit
detection output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
(to customer circuit)

Braking resistor
overheat switch

(thermal relay trip)

3-phase

TOBP_C720600_01C_3_0_E.fm 68 ページ 2013年11月1日 金曜日 午後2時50分