Yaskawa VS-616G5 Series Revision F Quick-Start User Manual
Page 98

VS-616G5 Installation & Quick-Start Manual
95
Gro
up F
O
pt
ions
Func
tion F
5 DO -
02 Setup
F5-01
Channel 1 Output
Selection
(DO-02 Ch1 Select)
00~37
1
0
—
x
A
A
A
A
F5-02
Channel 2 Output
Selection
(DO-02 Ch2 Select)
00~37
<26>
1
1
—
x
A
A
A
A
Fu
nc
tion F6
D
O
- 08 Se
tup
F6-01
Output Mode
Selection
(DO-08 Selection)
0, 1
1
0
0: (8ch Individual)
1: (Binary Output)
x
A
A
A
A
Func
tion F
7
PO -
36F
Setup
F7-01
Frequency Multiple
Selection
(PO-36F Selection)
0~4
1
1
0: (1 X Output Freq)
1: (6 X Output Freq)
2: (10 X Output Freq)
3: (12 X Output Freq)
4: (36 X Output Freq)
x
A
A
A
A
Fu
nc
tion F
8
SI - F
./G Setup
F8-01
SI-F/G
Communication
Error Detection
Operation Selection
(E-15 Det Sel)
0~3
1
1
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast - Stop)
3: (Alarm Only)
x
A
A
A
A
Func
tion F
9 CP-
916 Setup
/ DD
S • SI-
B
F9-01
Option External
Fault Selection
(EFO Selection)
0, 1
1
0
0: When 1 is shown, EFO
occurs (Normally Open)
1: When 0 is shown, EFO
occurs. (Normally Closed)
x
A
A
A
A
F9-02
Option External
Fault Detection
Selection
(EFO Detection)
0, 1
1
0
0: (Always Detected)
1: (Only During Run)
x
A
A
A
A
F9-03
Option External
Fault Detection
Operation Selection
(EFO Fault Action)
0~3
1
1
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast - Stop)
3: (Alarm Only)
x
A
A
A
A
F9-04
Trace Sampling
Time
(Trace Sample Tim)
0~
60000
1
0
—
x
A
A
A
A
F9-05
Torque Reference/
Torque Limit Selec-
tion through DP-
RAM communica-
tion (Torq Ref / Lmt
Sel)
0, 1
1
1
0: (Disabled)
1: (Enabled)
x
-
-
-
A
F9-06
DP-RAM Communi-
cation Error Detec-
tion Operation
Selection
(BUS Fault Sel)
0~3
1
1
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast - Stop)
3: (Alarm Only)
x
A
A
A
A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VS-616G5 Parameters