57
* For 460V class units, the value is twice that of 230V class units. For 575V class units the value is 2.5 times the 230V value.
* For 460V class units, the value is twice that of 230V class units. For 575V class units the value is 2.5 times the 230V value.
V/F Patterns for Inverter Capacity 55 ~ 300kW for 230V Class*
Parameter Name
Unit
Factory
Setting
E1-03
V/f Pattern Selec-
tion
–
0
1
2
3
4
5
6
7
E1-04
Max. Output Fre-
quency
Hz
50.0
<21>
60.0
60.0
72.0
<21>
50.0
<21>
50.0
<21>
60.0
60.0
E1-05
Max. Voltage
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Max. Voltage Fre-
quency
Hz
50.0
<21>
60.0
50.0
<21>
60.0
50.0
<21>
50.0
<21>
60.0
60.0
E1-07
Mid. Output Fre-
quency
V
2.5
<21>
3.0
3.0
3.0
25.0
<21>
25.0
<21>
30.0
30.0
E1-08
Mid. Output Fre-
quency Voltage
V
13.8
<21>
13.8
<21>
13.8
<21>
13.8
<21>
40.2
<21>
57.5
<21>
40.2
<21>
57.5
<21>
E1-09
Min. Output Fre-
quency
Hz
1.3
<21>
1.5
1.5
1.5
1.3
<21>
1.3
<21>
1.5
1.5
E1-10
Min. Output Fre-
quency Voltage
V
6.9
6.9
6.9
6.9
5.7
<21>
6.9
5.7
<21>
6.9
V/F Patterns for Inverter Capacity 55 ~ 300kW for 230V Class* (Continued)
Parameter Name
Unit
Factory
Setting
E1-03
V/f Pattern Selec-
tion
–
8
9
A
B
C
D
E
F
E1-04
Max. Output Fre-
quency
Hz
50.0
<21>
50.0
<21>
60.0
60.0
90.0
<21>
120.0
<21>
180.0
<21>
60.0
E1-05
Max. Voltage
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Max. Voltage Fre-
quency
Hz
50.0
<21>
50.0
<21>
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Mid. Output Fre-
quency
V
2.5
<21>
2.5
<21>
3.0
3.0
3.0
3.0
3.0
3.0
E1-08
Mid. Output Fre-
quency Voltage
V
17.2
<21>
23.0
<21>
17.2
<21>
23.0
<21>
13.8
<21>
13.8
<21>
13.8
<21>
13.8
<21>
E1-09
Min. Output Fre-
quency
Hz
1.3
<21>
1.3
<21>
1.5
1.5
1.5
1.5
1.5
1.5
E1-10
Min. Output Fre-
quency Voltage
V
8.0
<21>
10.3
<21>
8.0
<21>
12.6
<21>
6.9
6.9
6.9
6.9
Chapter 3 - Quick-Start Programming