VS-616G5 Installation & Quick-Start Manual

35

Wire and Terminal Screw Sizes (continued)

JST Closed Loop Connectors

Note 1:

The use of a JST closed-loop connector (lug) is recommended to maintain proper clearances. Please contact your Yaskawa repre-
sentative for more information.

Note 2:

Voltage drop should be considered when determining wire size. Voltage drop can be calculated using the following equation:

Select a wire size so that voltage drop will be less than 2% of the normal rated voltage.

Wire Size *

Terminal

Screw

JST Closed-Loop Connectors (Lugs)

Max. Torque

lb-in (N·m)

AWG

mm

2

20

0.5

M3.5

1.25 - 3.5

8.9 (1.0)

M4

1.25 - 4

12.4 (1.4)

18

0.75

M3.5

1.25 - 3.5

8.9 (1.0)

M4

1.25 - 4

12.4 (1.4)

16

1.25

M3.5

1.25 - 3.5

8.9 (1.0)

M4

1.25 - 4

12.4 (1.4)

14

2

M3.5

2 - 3.5

8.9 (1.0)

M4

2 - 4

12.4 (1.4)

M5

2 - 5

22.1 (2.5)

M6

2 - 6

45.1 (5.1)

M8

2 - 8

90.3 (10.2)

12 - 10

3.5 - 5.5

M4

5.5 - 4

12.4 (1.4)

M5

5.5 - 5

22.1 (2.5)

M6

5.5 - 6

45.1 (5.1)

M8

5.5 - 8

90.3 (10.2)

8

8

M5

8 - 5

22.1 (2.5)

M6

8 - 6

45.1 (5.1)

M8

8 - 8

90.3 (10.2)

6

14

M6

14 - 6

45.1 (5.1)

M8

14 - 8

90.3 (10.2)

4

22

M6

22 - 6

45.1 (5.1)

M8

22 - 8

90.3 (10.2)

3 - 2

30 - 38

M8

38 - 8

90.3 (10.2)

1 - 1/0

50 - 60

M8

60 - 8

90.3 (10.2)

M10

60 - 10

203.6 (23.0)

3/0

80

M10

80 - 10

203.6 (23.0)

4/0

100

100 - 10

203.6 (23.0)

4/0

100

M12

100 - 12

349.6 (39.5)

300MCM

150

150 - 12

349.6 (39.5)

400MCM

200

200 - 12

349.6 (39.5)

650MCM

325

M12 x 2

325 - 12

349.6 (39.5)

M16

325 - 16

867.4 (98.0)

Phase-to phase voltage drop (V)

wire resistance (

Ω/km) x wiring distance (m) x current (A) x 10

-3

3

=

Chapter 1 - Receiving & Installation

Wiring