Yaskawa VS-616G5 Series Revision F Quick-Start User Manual
Page 53

50
VS-616G5 Installation & Quick-Start Manual
· DC Injection Braking Stop (B1-03 = “2”)
Upon removal of the FWD (REV) run command, the motor brakes to stop, according to the DC injec-
tion braking time at stop set in B2-04. If this value is set to “0” (factory default), DC injection braking
is disabled, and the motor coasts to stop. When choosing this function, note that the actual stop time
from maximum frequency is the time set in B2-04 multiplied by 10 (see the figure above). This stop-
ping method is disabled during flux vector control.
· Coast to Stop with Timer 1 (B1-03 = “3”)
After a stop command is given, a run command is not accepted while the coast to stop timer C1-02
elapses (same as Decel Time 1). After the timer runs out, another run command must be given for the
inverter to begin acceleration. This stopping method is disabled during flux vector control.
Output Frequency
Run Command
ON
OFF
DC injection Braking Time
at Stop (B2-04)
Factory Default: 0.0s
Minimum Baseblock Time (L2-03)
Factory Default: 0.5s
Inverter Output OFF during
Figure 21 Stopping Method - DC Injection Braking Stop
DC injection Braking Time
at Stop (B2-04)
DC injection
Braking Time
B2-04 x 10
F
max
(E1-04)
F
out
Output Frequency
Coasting
Decel Time 1
(C1-02)
Accel Time 1
(C1-01)
Time
ON
ON
ON
FWD (REV)
Run Command
Run Command Disabled
Figure 22 Stopping Method - Coast to Stop w/ Timer
Chapter 3 - Quick-Start Programming
Programming Menu