Custom V/f Pattern
Set up a custom V/f pattern by setting parameter E1-03 to “F”, and then setting the values in parame-
ters E1-04 to E1-10.
* For 460V class units, the value is twice that of 230V class units. For 575V class units the value is 2.5 times the 230V value.
Increasing the voltage in the V/f pattern increases motor torque. However,
when setting a custom
V/f pattern, increase the voltage gradually while monitoring the motor current, to prevent
:
· Inverter fault trips as a result of motor overexcitation
· Motor overheat or excessive vibration
V/f
Control
V/f
w/ PG
Open Loop
Vector
Flux
Vector
E1-04 Maximum Frequency
Max Frequency
√
√
√
√
E1-05 Maximum Voltage
Max Voltage
√
√
√
√
E1-06 Maximum Voltage Output Frequency
Base Frequency
√
√
√
√
E1-07 Middle Output Frequency
Mid Frequency A
√
√
−
−
E1-08 Middle Output Voltage
Mid Voltage A
√
√
−
−
E1-09 Minimum Output Frequency
Min Frequency
√
√
√
−
E1-10 Minimum Output Voltage
Min Voltage
√
√
−
−
E1-13 Motor Base Voltage
Base Voltage
−
−
√
√
Parameter
No.
Name
Unit
Setting Range
Factory
Default
E1-04
Maximum output frequency
0.1 Hz
50.0 to 400 Hz
60.0 Hz
E1-05
Maximum voltage
0.1 V
0.1 to 255 V *
230 V *
E1-06
Maximum voltage output frequency
(base frequency)
0.1 Hz
0.2 to 400 Hz
60.0 Hz
E1-07
Mid. output frequency
0.1 Hz
0.1 to 399 Hz
3.0 Hz
E1-08
Mid. output frequency voltage
0.1 V
0.1 to 255 V *
17.2 V *
E1-09
Minimum output frequency
0.1 Hz
0.1 to 10.0 Hz
1.5 Hz
E1-10
Minimum output frequency voltage
0.1 V
0.1 to 50.0 V *
10.3 V *
Be sure to satisfy the following conditions
for setting parameters E1-04 to E1-10:
E1-09
≤ E1-07 < E1-06 ≤ E1-04
0
E1-09 E1-07 E1-06
E1-04
Frequency
Voltage
E1-10
E1-08
E1-05
Figure 23 Custom V/f Pattern Setting