MAINTENANCE & INSPECTION
This section describes basic maintenance and inspection procedures for the VS-616G5.
Periodic Inspection
The VS-616G5 will function longer if it is kept clean, cool and dry, and if all precautions highlighted
in this manual are observed. Periodically inspect the inverter as described in the table below to prevent
accidents and to ensure high performance with high reliability.
To prevent electrical shock, disconnect all power before servicing the inverter. Then wait at least five
minutes after the power supply is disconnected and all LEDs are extinguished.
Parts Replacement Schedule
Replace the following parts periodically, for long, safe, trouble-free operation of the VS-616G5:
Optimum operating conditions:
Ambient temperature: 86°F yearly average
Load factor:
80% or below
Operation rate:
12 hours or less per day
Component
Check
Corrective Action
External Terminals,
Connectors, Mounting
Screws, etc.
Loose screws or connectors
Securely tighten.
Heatsink
Build-up of dust and dirt
Blow with dry, compressed air [39.2
× 10
4
to 58.8
× 10
4
Pa (4 to 6kg·cm
2
)
pressure].
Printed Circuit Board
(PCB)
Accumulation of conductive dust or oil
Blow with dry, compressed air [39.2
× 10
4
to 58.8
× 10
4
Pa (4 to 6kg·cm
2
)
pressure]. If dust and oil cannot be
removed, replace the board.
Cooling Fan
For abnormal noise and vibration
Replace the cooling fan.
Power Components
Accumulation of dust and dirt
Blow with dry, compressed air [39.2
× 10
4
to 58.8
× 10
4
Pa (4 to
6kg·cm2) pressure].
Smoothing Capacitor
Discoloration or odor
Replace the capacitor or the inverter.
Parts
Approximate Interval
Remarks
Cooling Fan
2 to 3 years
Replace with new one.
Smoothing Capacitor
5 years
Replace with new one (after inspection).
Breakers or Relays
--
Decide after inspection.
Fuses
10 years
Replace with new one.
Aluminum Electrolytic
Capacitor on PCB Board
5 years
Replace with new one (after inspection).
Chapter 4 - Diagnostics