VS-616G5 Installation & Quick-Start Manual

Control Circuit Wiring

The table below outlines the functions of the control circuit terminals.

Control Circuit Terminals

Classification Terminal

Signal Function

Description

Signal Level

Sequence

Input Signal

1

Forward run/stop

Forward run when closed, stop when open (2-wire configuration)

Photo-coupler insulated

Input: +24VDC, 8mA

2

Reverse run/stop

Reverse run when closed, stop when open (2-wire configuration)

3

External fault input

Fault when closed, normal state

when open

Multi-function contact inputs

(H1-01 to H1-06)

4

Fault reset input

Reset when closed

5

Master/Aux. change

Multi-step speed ref.1)

Aux. freq. ref. when closed

6

Multi-step speed ref.2

Effective when closed

7

Jog reference

Jog run when closed

8

External baseblock

Inv. output baseblocked when closed

11

Sequence control input common

terminal

Analog

Input Signal

15

+15V

Power supply output

For analog command +15V power supply

+15V (Allowable current

20mA max.)

33

-15V

Power supply output

For analog command -15V power supply

-15V (Allowable current

20mA max.)

13

Master frequency ref. (voltage)

-10 to +10V/-100% to +100%

0 to +10V/100%

-10 to +10V (20k

Ω),

0 to +10V/(20k

Ω)

14

Master frequency ref. (current)

4 to 20mA/100%.

Multi-function analog input (H3-
08,
H3-09,
H3-10, H3-11
)

4 to 20mA (250

Ω)

16

Multi-function analog input

-10 to +10V/-100% to +100%

0 to +10 V/100%

Multi-function analog input (H3-
04,
H3-05,
H3-06, H3-07
)

-10 to +10V (20k

Ω),

0 to +10V/(20k

Ω)

17

Common terminal for control circuit 0V

12

Connection to shield sheath of

signal lead

Sequence

Output

Signal

9

During running (NO contact)

Closed when running

Multi-function output

(H2-01 to H2-03)

Dry contact

Contact capacity:

250VAC, 1A or less

30VDC, 1A or less

10

25

Zero speed detection

Activates at min. freq. (E1-09) or less

Open collector output

48V, 50mA or less

26

Speed agree detection

Activates when the freq. reaches to

±1Hz of set freq.

27

Open collector output common

18

Fault contact output

(NO/NC contact)

When faulted closed between terminals 18 and 20

When faulted open between terminals 19 and 20

Dry contact

Contact capacity:

250VAC, 1A or less

30VDC, 1A or less

19
20

Analog

Output

Signal

21

Frequency meter output

0 to ±10V/100% frequency

Multi-function analog

monitor 1 (H4-01, H4-02, H4-03)

0 to ±11V Max. ±5%

2mA or less

22

Common

23

Current monitor

5V/inverter rated current

Multi-function analog

monitor 2 (H4-04, H4-05, H4-06)