Hardware, Microtrac hub card – Yaskawa Modicon 800 Series Remote I/O Network for use on Microtrac LAN User Manual
Page 8

Table 4. MicroTrac Hub Card Setup
CR1
bnc1 MicroTrac LAN port is active
(red)
(used either as the input or one of the outputs)
CR2
bnc2 MicroTrac LAN port is active
(red)
(used either as the input or one of the outputs)
LEDs
CR3
bnc3 MicroTrac LAN port is active
(red)
(used either as the input or one of the outputs)
CR4
bnc4 MicroTrac LAN port is active
(red)
(used either as the input or one of the outputs)
CR5
signals reconfigure on the MicroTrac LAN
(yellow)
(light on when reconfiguring)
CR6
LAN timing light – usually on
(red)
(if off, problem with LAN timing)
E1
e
enables LAN driver (default)
d
disables LAN driver (used during testing)
m
select Hub card as master (default)
E4
s
select Hub card as slave
(used when connecting more than one card together)
E6
e
enables LAN driver (default)
Jumpers
d
disables LAN driver (used during testing)
con
selects top connector (conn)
E8
for master/slave timing signals (default)
bus
selects the computer bus for master/slave timing signals
conv
converts the +5V to –5V for use by the card
E9
when not in the bus configuration
bus
does not convert the +5V to –5V; takes –5V
from computer bus (default)
response time-out (msec)
reconfigure time-out (msec)
nor
74.7
840 (default)
E10
et1
283.4
1680
et2
561.8
1680
et3
1118.6
1680
bnc1-4
MicroTrac LAN connection
Connectors
(used either as the input or one of the outputs)
conn
used to connect other Hub cards together
in the master/slave configuration
2
HARDWARE
7
5/24/96
MicroTrac Hub Card
M i c r o Trac Hub
C a r d
( c o n t i n u e d )
RD 3004-20