OPERATION

21

PLC Gateway Status

5/24/96

display

meaning

EARC

Displayed during PLC gateway initialization if the MicroTrac
card is not found. Initialization is not completed.

Troubleshoot: Check that the interface card has been

installed properly. The card could be defective;
replace it with another.

ECOM

Appears during operation if the interface card is not
communicating with the Modicon PLC.

Troubleshoot: Check the cabling between the interface

card and the Remote I/O Processor. Is the
Modicon PLC in the RUN mode?

ECdd

This indicates that the PLC gateway is unable to get a
configuration from the Modicon PLC for drop "dd".

When the PLC gateway receives an allocation message from
the MicroTrac LAN, it decodes the channel number into a
drop and slot number. It then attempts to get a configuration
for that drop from the Modicon PLC. If it cannot, this error
message is displayed and the PLC gateway hangs.

Troubleshoot: Check the cabling between the interface

card and the Remote I/O Processor.

• Is the Modicon PLC on? Has it been programmed?

Check the configuration on Traffic Cop.

• Does the configuration include the drop(s) being

allocated? Is the drop being scanned? Check the
segment scheduler.

• Is the Remote I/O Processor COM ERROR light

on? It should be on until the interface card has
received a configuration for each simulated drop.

• Is the drop you are trying to configure remote?

For some PLCs, drop 1 is local and cannot be
programmed. Also remember to use only drops
2-24, rack 2, slots 1-9.

PLC Gateway

Status

(continued)

RD 3004-20