Appendix 3- parameter cross reference, Parameter name, Description or selection – Yaskawa GPD506/P5 to P7 User Manual
Page 45

Appendix 3- Parameter Cross Reference
Page
45
of 48
GPD506/P5 Parameter
P7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
100
Time of average
KW
Set unit:1 (1=25ms)
Set range: 1-200 (25ms=5.0sec)
0 to 2000
Used to fine-tune the energy savings
function when in V/F control method.
Power Detection Filter Time
b8-05
101
MEMOBUS timeout
detection
0: Timeout detection disabled.
1: Timeout detection enabled.
Enables or disables the communications
timeout fault (CE).
0: Disabled - A communication loss will
not cause a communication fault.
1: Enabled - If communication is lost for
more than 2 seconds, a CE fault will
occur.
Communication Error
Detection
Selection
H5-05
102
MEMOBUS Stop
method selection at
communication error (CE)
0: Deceleration stop
(Decelerate by deceleration time 1)
1: Coast stop
2: Deceleration stop
(Decelerate by deceleration time 2)
3: Continue operation (alarm display)
Selects the stopping method when a
communication timeout fault (CE) is
detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Run at d1-04
Stopping Method after
Communication Error
H5-04
104
MEMOBUS
Slave address
Set unit:1 Set range:0-31
(There is no MEMOBUS communication at
set point =0)
0 to 20 Hex
Selects Drive station node number
(address) for Modbus terminals R+, R-, S+,
S-. The Drive’s power must be cycled for
the setting to take effect.
Drive Node Address
H5-01
105
MEMOBUS
Baud rate selection
0: 2400bps
1: 4800bps
2: 9600bps
Selects the baud rate for Modbus terminals
R+, R-, S+ and S-. The Drive’s power must
be cycled for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
Communication Speed
Selection
H5-02
106
MEMOBUS
Parity selection
0: Parity none
1: Even parity
2: Odd parity
Selects the communication parity for
Modbus terminals R+, R-, S+ and S-. The
Drive’s power must be cycled for the
setting to take effect.
0: No Parity
1: Even Parity
2: Odd Parity
Communication Parity
Selection
H5-03
108
Motor no-load current
Set unit: 1%
Set range: 0-99%
(100%= rated current of motor)
Set to the magnetizing current of the motor
as a percentage of full load amps (E2-01).
This value is automatically set during
rotational Auto-Tuning.
No-Load Current
E2-03
110
Operator Connection Fault
Detect Select
0: Operator connection fault disabled.
1: Operator connection fault enabled.
Determines if the Drive will stop when the
Digital Operator is removed when in
LOCAL mode or b1-02=0.
0: Disabled - The Drive will not stop when
the Digital Operator is removed.
1: Enabled - The Drive will fault (OPR)
and coast to stop when the operator is
removed.
Operation Selection when
Digital
Operator is Disconnected
o2-06
111
Local/remote Change- over
function Select
0: Cycle External run
1: Accept external run
0: Cycle External RUN - If the run
command is closed when switching from
local mode to remote mode, the Drive
will not run.
1: Accept External RUN - If the run
command is closed when switching
from local mode to remote mode, the
Drive will run.
Local/Remote Run Selection
b1-07
112
Low frequency OL
starting point
Set unit: 0.1Hz
Set range: 0.0-10.0Hz
113
Continuous running
level at 0Hz
Set unit: 1%
Set range: 25-100%
This parameter assists in protecting the
output transistors from overheating when
output current is high and output frequency
is low (6Hz and less).
0: Disabled
1: Enabled (L8-18 is active)
OL2 Characteristic Selection
at
Low Speeds
L8-15