Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD506/P5 to P7 User Manual
Page 35

Appendix 3- Parameter Cross Reference
Page
35
of 48
GPD506/P5 Parameter
P7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
(con’t)
037
Multi-function contact input 2
(terminal S3)
Set range: 2-28
(It is the same as constant n036)
Open = Only speed command at U1-01 can
be changed.
1C: TrimCtl Increase
Closed = Increase motor speed by value in
d4-02.
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04
as a speed command.
Must be used in conjunction with Trim Ctrl
Decrease.
1D: Trim Ctl Decrease
Closed = Decrease motor speed by value in
d4-02
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04
as speed command.
Must be used in conjunction with Trim Ctrl
Increase.
1E: Ref Sample Hold
Analog speed command is sampled then
held at time of input
closure.
20: External fault, Normally Open, Always
Detected, Ramp To
Stop
21: External fault, Normally Closed,
Always Detected, Ramp To
Stop
22: External fault, Normally Open, During
Run, Ramp To Stop
23: External fault, Normally Closed,
During Run, Ramp To Stop
24: External fault, Normally Open, Always
Detected, Coast To
Stop
25: External fault, Normally Closed,
Always Detected, Coast To
Stop
26: External fault, Normally Open, During
Run, Coast To Stop
27: External fault, Normally Closed,
During Run, Coast To Stop
28: External fault, Normally Open, Always
Detected, Fast-Stop
29: External fault, Normally Open, Always
Detected, Fast-Stop
2A: External fault, Normally Open, During
Run, Fast-Stop
2B: External fault, Normally Closed,
During Run, Fast-Stop
2C: External fault, Normally Open, Always
Detected, Alarm Only
2D: External fault, Normally Closed,
Always Detected, Alarm
Only
2E: External fault, Normally Open, During
Run, Alarm Only
2F: External fault, Normally Closed,
During Run, Alarm Only
30: PI Integral Reset
Resets the PI Integral component to zero
when closed
31: PI Integral Hold
Holds the PI integral value when closed
34: PI SFS Cancel (SFS= SoftStart, also
called Accel/Decel,
See Parameter b5-17)
35: PI Input Level Sel
Inverts the PI error signal when closed
36: Option/Inv Sel 2 Selects source of
speed command and
sequence
Closed = b1-01 & b1-02, Open = Option
Card
Multi-Function Digital Input
Terminal S3 Function
Selection
H1-01