Appendix 3- Parameter Cross Reference

Page

34

of 48

GPD506/P5 Parameter

P7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

(con’t)

037
















































Multi-function
contact input 2
(terminal S3)






































































Set range: 2-28







































































6: Jog Freq Ref
Closed = speed command from d1-17
Open = speed command determined by b1-
01
7: Multi-Acc/Dec 1
Closed = Accel & Decel Ramps
determined by C1-03 & C1-04,
Open = Accel & Decel Ramps determined
by C1-01 & C1-02
8: Ext BaseBlk N.O.
Closed = Output transistors forced off,
Open = Normal operation
9: Ext BaseBlk N.C.
Closed = Normal Operation, Open =
Output transistors forced
off
A: Acc/Dec RampHold
Closed = Acceleration suspended and
speed held, Open =
Normal Operation
C: Term A2 Enable
Closed = Terminal A2 is active, Open =
Terminal A2 is disabled
F: Term Not Used
Terminal has no effect
10: MOP Increase
Closed = Speed Command Increases, Open
= Speed Command
Held.
Must be set in conjunction with MOP
Decrease and b1-02 must
be set to 1.
11: MOP Decrease
Closed = Speed Command Decreases,
Open = Speed Command
Held.
Must be set in conjunction with MOP
Increase and b1-02 must
be set to 1.

12: Forward Jog
Closed = drive runs forward at speed
command entered into
parameter d1-17.
13: Reverse Jog
Closed = drive runs in reverse at speed
command entered into
parameter d1-17.
14: Fault Reset
Closed = Resets the drive after the fault
and the run
command have been removed.
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09,
regardless of run
command status.
17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09,
regardless of run
command status.

Closed = Normal operation
Open = Drive decelerates using C1-09,
regardless of run command status.
18: Timer Function
Input for independent timer, controlled by
b4-01 and b4-02.
Used in conjunction with a multi-function
digital output.
19: PI Disable
Turns off the PI controller, and PI setpoint
becomes speed command.
1B: Program Lockout
Closed =All parameter settings can be
changed.


Multi-Function Digital Input
Terminal S3 Function
Selection





































































H1-01