SMA Off-Grid Systems User Manual

Page 32

background image

5  Single-Cluster System

SMA Solar Technology AG

32

Off-Grid-IS-en-30

Installation - Quick Reference Guide

Set the nominal voltage of the battery.

Set the battery capacity for ten-hour electric discharge

(for determining the battery capacity, see the Sunny Island

inverter installation manual).

Set the battery capacity for ten-hour electric discharge

(for determining the battery capacity, see the Sunny Island

inverter installation manual).

Set the grid voltage and power frequency of the stand-alone grid:

230V_50Hz: grid voltage 230 V, power frequency 50 Hz

220V_60Hz: grid voltage 220 V, power frequency 60 Hz

Set the number of line conductors in the system:

1Phase: single-phase off-grid system

3Phase: three-phase off-grid system

Set SingleClst.

Set the type of energy sources.

PvOnly: no generator is connected to terminal AC2 of the

Sunny Island inverter.

Gen: one generator is connected to terminal AC2 of the

Sunny Island inverter.